Intended Use; Product Description; Product Features - Dräger REGARD 2400 Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 67
2

Intended use

The REGARD 2400/2410 is used for continuous, stationary monitoring of flammable, toxic gases
and vapours as well as of oxygen deficiency and enrichment, for displaying measured values on
the display and to issue alarm signals via the relays.
DANGER
!
The REGARD 2400/2410 is not designed or authorised for use in areas where
flammable or explosive gas mixtures could develop. Explosion hazard!
3

Product description

The REGARD 2400/2410 is a freely programmable gas monitoring and warning system with
rolling display for connecting up to 4 transmitters. Various types of gas can also be monitored
with a gas monitoring and warning system. It can be operated with 1 or 2 alarm thresholds.
The REGARD 2400/2410 has 4 relays. 2 of these can be freely assigned. One relay is reserved
for a horn and another for a fault message.
4

Product features

Construction type for DIN-rail or wall mounting
Voltage supply 24 VDC, 110 VAC, 230 VAC
4 transmitters maximum 4-20 mA or Polytron SE Ex
1 fault relay
1 horn relay
Up to 2 alarm messages via relays
Up to 2 limit values freely selectable
Latching, with hysteresis or impulse
Concentration display
Checking of the output relays
Wire and short-circuit monitoring of the transmitter line
1 reset button for horn and alarm
LED for alarm, horn and fault
Communication port for optional modules
2 digital inputs
Dräger REGARD 2400/2410
Intended use
37

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Regard 2410

Tabla de contenido