WARNING
!
The switch-on delay is used to suppress fluctuating concentrations around the triggering
threshold.
12.3
Expansion modules (optional)
Relay module: Addressing takes place automatically via the software. Address assignment is
between 4 and 7. In addition, the corresponding address must be set manually for each dip switch
on the relay module. (See corresponding section in the REGARD 2400/2410 operating manual).
I/O module: Addressing is automatically set to 8 and cannot be changed.
12.3.1
Relay module
Relay 1:
General alarm Relay 1
Relay 2:
General alarm Horn relay
Relay 3:
General alarm Fault relay
Relay 4:
Channel A Individual alarm 1
Relay 5:
Channel A Horn relay
Relay 6:
Channel A Fault relay
Relay 7:
Transfer of the digital input DE1
Relay 8:
Transfer of the digital input DE3 from the optional I/O module
Relay 9:
Inhibit on/off, the relay switches when this function is called up.
Relay 10:
Copy of the signal's on/off average value, the relay switches when this function
is called up.
Relay 11:
Copy of the signal's on/off relay test, the relay switches when this function
is called up.
Relay 12:
Deactivated
Inverted:
On activation the signals of the controller are inverted
(for example: normally energised to energised on alarm).
12.3.2
I/O module
Output 1:
Analogue 4 – 20 mA output for Channel A
Output 2:
Analogue 4 – 20 mA output for Channel A average determination
Output 3:
Analogue 4 – 20 mA output of the power supply 0 – 30 V
Output 4:
Deactivated
Digital inputs:
See "Digital Input DE configuration" on page 55.
Dräger REGARD 2400/2410
Configuration software
57