Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 67

Technical data

14
Technical data
Dräger REGARD 2410
Supply voltage
Power consumption without
connected sensors
4-20 mA input channels
Digital inputs
Input
Output relay
Relay contacts
Ambient conditions
Display tolerance
Cable connection
Dimensions (H x W x D)
Material
Protection class
Approvals
(see "Approvals" on page 229)
Dräger REGARD 2400
Supply voltage
Power consumption without
connected sensors
4-20 mA input channels
Digital inputs
Input
64
: 24 VDC ±10 %
: Approx. 2.5 W
: 4
: 2
: 4-20 mA, input load 350 Ω
: Fault at <3.5 mA
: Fault at >23 mA
: Hysteresis for fault 0.2 mA
: Alarm 1 to 2
: Error
: Horn
: Floating 250 VAC, 2 A
: Temperature: –20 °C to 60 °C
: Humidity: 10 to 90 % r.h.
: The deviations for the display Controller-Display →Transmitter-
Display are <2 %
: Screw terminals single-wire up to 4 mm
fine-wire up to 2.5 mm
: 90 mm x 105 mm x 72 mm
: Plastic
: IP20
ATEX: II (2) G according to TPS 14 ATEX 1 672 X as per
EN 60079-29-1:2007; EN 50271:2010 and EN 50104:2010
EMC: EMC Directive (2004/108/EC) and Low Voltage Directive
(2006/95/EC)
: 110/230 VAC ±10 %, 50Hz or 24 VDC
: Approx. 3 W
: 4
: 2
: 4-20 mA, input load 350 Ω
: Fault at <3.5 mA
: Fault at >23 mA
: Hysteresis for fault 0.2 mA
2
2
Dräger REGARD 2400/2410

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Regard 2410

Tabla de contenido