2.4
Bluetooth radio interface
2.5
Min. inlet pressure
Installation and operating instructions Wilo-Stratos MAXO/-D/-Z
Description of the pump
Technical data for drinking water
Fig. 5: Technical data for drinking water
Technical data
Permissible fluid temperature
Permitted ambient temperature
Maximum relative humidity
Mains voltage
Residual current ∆I
Electromagnetic compatibility
Emissions-sound-pressure level
Energy efficiency index (EEI)
Temperature class
Pollution degree
Max. permitted operating pressure
*
EEI value of the pump is achieved when the display is switched off.
1)
Standard version
2)
Special version or auxiliary equipment (at additional charge)
Table 4: Technical data for drinking water
For further instructions see rating plate and catalogue.
The pump has a Bluetooth interface for connecting to mobile devices. Using an app and
a smartphone, you can operate and adjust the pump and read out pump data. Bluetooth
is active by factory default and can, if required, be deactivated via the Settings/Device
settings/Bluetooth menu.
▪ Frequency band: 2400 MHz – 2483.5 MHz
▪ Maximum radiated transmission power: < 10 dBm (EIRP)
Minimum inlet pressure (above atmospheric pressure) at the pump's suction port to
avoid cavitation noises at fluid temperature:
Nominal diameter
Fluid temperature
-10 °C to +50 °C
0.3 bar
Rp 1
0.3 bar
Rp 1¼
DN 32 (H
= 8 m,
0.3 bar
max
10 m, 12 m)
0 to +80 °C
0 to +40 °C
95 % (non-condensing)
1~ 230 V +/-10 % 50/60 Hz
≤ 3.5 mA
Emitted interference in acc. with:
EN 61800-3:2004+A1:2012 / residential
environment (C1)
Interference resistance in acc. with:
EN 61800-3:2004+A1:2012 / industrial en-
vironment (C2)
< 54 dB(A)
*
≤ 0.17 to ≤ 0.19 (depends on type)
TF110 (see IEC60335-2-51)
2 (IEC 60664-1)
1)
PN 6/10
, PN 16
+80 °C
0.8 bar
0.8 bar
0.8 bar
en
2)
+95 °C
+110 °C
1.0 bar
1.6 bar
1.0 bar
1.6 bar
1.0 bar
1.6 bar
121