Scope Of Delivery - Wilo Stratos MAXO Instrucciones De Instalación Y Funcionamiento

Ocultar thumbs Ver también para Stratos MAXO:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

en
2.6

Scope of delivery

122
Description of the pump
Nominal diameter
Fluid temperature
-10 °C to +50 °C
0.5 bar
DN 32 (H
= 16 m)
max
DN 40 (H
= 4 m,
0.3 bar
max
8 m)
DN 40 (H
= 12 m,
0.5 bar
max
16 m)
0.3 bar
DN 50 (H
= 6 m)
max
0.5 bar
DN 50 (H
= 8 m)
max
DN 50 (H
= 9 m,
0.5 bar
max
12 m)
DN 50 (H
= 14 m,
0.7 bar
max
16 m)
DN 65 (H
= 6 m,
0.5 bar
max
9 m)
DN 65 (H
= 12 m,
0.7 bar
max
16 m)
0.7 bar
DN 80
0.7 bar
DN 100
Table 5: Min. inlet pressure
NOTICE
Effective up to 300 m above sea level. For higher altitudes +0.01 bar/100 m.
In case of higher fluid temperatures, fluids of lower density, higher flow resistances
or lower atmospheric pressure, adjust the values accordingly.
The maximum installation height is 2000 metres above MSL.
Fig. 6: Scope of delivery single pumps
+80 °C
+95 °C
+110 °C
1.0 bar
1.2 bar
1.8 bar
0.8 bar
1.0 bar
1.6 bar
1.0 bar
1.2 bar
1.8 bar
0.8 bar
1.0 bar
1.6 bar
1.0 bar
1.2 bar
1.8 bar
1.0 bar
1.2 bar
1.8 bar
1.2 bar
1.5 bar
2.3 bar
1.0 bar
1.2 bar
1.8 bar
1.2 bar
1.5 bar
2.3 bar
1.2 bar
1.5 bar
2.3 bar
1.2 bar
1.5 bar
2.3 bar