DIP switches ds2 and ds1 are reserved for the selection of stand-alone, parallel
or
3-phase operation
Stand-alone operation
Step 1: Setting ds2 and ds1 for stand-alone operation
DS-8 AC input
Set as desired
DS-7 AC input
Set as desired
DS-6 AC input
Set as desired
DS-5 AES
Set as desired
DS-4 Charging current Set as desired
DS-3 Charging current Set as desired
DS-2 Stand-alone operation
DS-1 Stand-alone operation
Examples of DIP switch settings for stand-alone mode are given below.
Example 1 shows the factory setting (since factory settings are entered by computer,
all DIP switches of a new product are set to 'off').
Four examples of stand-alone settings:
DS-8 AC input
DS-7 AC input
DS-6 AC input
DS-5 AES
DS-4 Ch. current
DS-3 Ch. current
DS-2 St.-alone mode
DS-1 St.-alone mode
Step1, stand-alone
Example 1 (factory setting):
8, 7, 6 AC-in-1: 30A
5 AES: off
4, 3 Charging current: 75%
2, 1 Stand-alone mode
To store the settings after the required values have been set: press the 'Up' button for
2 seconds (upper button to the right of the DIP switches, see appendix A, position K).
The overload and low-battery LED's will flash to indicate acceptance of the
settings.
We recommend making a note of the settings, and filing this information in a safe
place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
on
DS-8
on
on
DS-7
on
on
DS-6
on
off
DS-5
on
DS-4
on
off
DS-3
on
off
DS-2
off
DS-1
Step1, stand-alone
Example 2:
8, 7, 6 AC-in-1: 30A
5 AES: off
4, 3 Charge: 100%
2, 1 Stand-alone
off
off
DS-8
DS-7
on
DS-6
on
off
DS-5
DS-4
on
DS-3
on
off
DS-2
off
DS-1
Step1, stand-alone
Example 3:
8, 7, 6 AC-in-1: 12A
5 AES: off
4, 3 Charge: 100%
2, 1 Stand-alone
off
DS-8
on
DS-7
on
DS-6
off
off
DS-5
on
DS-4
off
DS-3
on
off
DS-2
off
off
DS-1
off
Step1, stand-alone
Example 4:
8, 7, 6 AC-in-1: 25A
5 AES: on
4, 3 Charge: 50%
2, 1 Stand-alone
27