meaning of different parameters
code description
Values (bold = default)
P01 Complete cycle operating
0: sequential
mode
1: sequential + timed close
2: semiautomatic
3: automatic
4: automatic + cell blocking
5: deadman's control (wire)
P02 Complete operating mode
0 to 30 (value x 10 s = time delay value)
automatic timed closing
2: 20 s
P03 Pedestrian cycle operating
0: ident. to complete cycle operating mode
mode
1: without automatic closing
2: with automatic closing
P04 Short automatic closing time
0 to 30 ( value x 10 s = time delay value)
delay in pedestrian cycle
2: 20 s
P05 Long automatic closing time
0 to 99 ( value x 5 min = time delay value)
delay in pedestrian cycle
0: 0 s
P06 Pedestrian opening
1: minimum pedestrian opening
amplitude
9: maximum pedestrian opening
1: 80 cm
P07 Cell safety input
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply switching
4: bus cells
P08 Safety edge safety input
0: inactive
1: active
2: active with auto-test
P09 Programmable safety input
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply switching
P10 Programmable safety input
0: active closing
- function
1: active opening
2: active closing + ADMAP
3: all movement disabled
P11 Programmable safety input
0: stop
- action
1: stop + partial reversal
2: stop + complete reversal
P12 Orange warning light
0: no warning
1: with 2 s warning prior to movement
operating code display
code description
c1
Awaiting command
c2
Gate opening
c3
Awaiting gate closure
c4
Gate closing
c6
Detection in progress for cell safety
c7
Detection in progress for safety edge safety
c8
Detection in progress for programmable safety
c9
Detection in progress for emergency stop safety
c12
Reinjecting current
c13
Safety device autotest in progress
c14
Permanent complete opening wire control input
c15
Permanent pedestrian opening wire control input
c16
BUS cell programming refused
cc1
9.6 V power supply
cu1
24 V power supply
Fault and breakdown code display
code
description
e1
Cell safety autotest fault
e2
Programmable safety autotest fault
e3
Defective safety edge autotest
e4
Obstacle detection when opening
e5
Obstacle detection when closing
e6
Cell safety fault
e7
Safety edge safety fault
e8
Programmable safety fault
e10
Motor short circuit protection
e11
24V power supply short protection
e12
Hardware fault
e13
Accessories power supply fault
e15
Fault when the control box supplied by
the backup battery is first switched on
access to memorised data -
data
description
u0 to u1
Complete opening cycle counter
u2 to u3
u6 to u7
Cycle counter with obstacle
detection
u8 to u9
u12 to u13
Partial opening cycle counter
u14 to u15
Reset movement counter
u20
Number of remote controls memorised for complete opening control
u21
Number of remote controls memorised for pedestrian opening control
u22
Number of remote controls memorised for remote lighting control
u23
Number of remote controls memorised for auxiliary output control
d0 to d9
Log of the last 10 faults (d0 most recent - d9 oldest)
dd
To clear the fault log: press and hold "ok" for 7 s.
setting
compl.
comments
The cell autotest is not satisfactory.
The programmable safety input autotest is not
satisfactory.
The safety edge autotest is not satisfactory.
Detection in progress on safety input for longer than 3
minutes.
Product and additional devices connected to terminals
21 to 26 not operating
The hardware auto tests are not satisfactory
The accessories power supply cuts out following an
overload (excessive consumption).
To access memorised data, select parameter "ud" and press "ok".
global [Hundred thousands - ten thousands - thousands] [hundreds - tens - units]
since last auto-programming [Hundred thousands - ten thousands - thousands] [hundreds - tens - units]
global [Hundred thousands - ten thousands - thousands] [hundreds - tens - units]
since last auto-programming [Hundred thousands - ten thousands - thousands] [hundreds - tens - units]
code description
Values (bold = default)
P13 Area lighting output
0: inactive
1: controlled operation
2: automatic + controlled operation
P14 Area lighting time delay
0 to 60 (value x 10 s = time delay value)
6: 60 s
P15 Auxiliary output
0: inactive
1: automatic: gate open indicator light
2: automatic: timed bistable
3: automatic: one-touch
4: controlled: bistable (ON-OFF)
5: controlled: one-touch
6: controlled: timed bistable
P16 Auxiliary output time delay
0 to 60 (value x 10 s = time delay value)
6: 60 s
P19 Closing speed
1: slowest speed at
10: highest speed - default value: 5
P20 Opening speed
1: slowest speed at
10: highest speed - default value: 5
P21 Closing slowdown zone
1: shortest slowdown zone at
5: longest slowdown zone
default value: 1
P22 Opening slowdown zone
1: shortest slowdown zone at
5: longest slowdown zone
default value: 1
P25 Closing torque limitation
P26 Opening torque limitation
1: minimum torque at
P27 Closing slowdown torque
10: maximum torque
limitation
adjusted when auto-programming complete
P28 Opening slowdown torque
limitation
P33 Obstacle detection sensitivity 0: low sensitivity
1: low sensitivity
2: standard
3: high sensitivity
P37 Wired control inputs
0: complete cycle mode - pedestrian cycle
1: opening mode - closing
P40 Coupling speed when closing 1: slowest speed at
P41 Coupling speed when
4: fastest speed
default value: 2
opening
Programming code display
code description
h0
Awaiting setting
hc1
Awaiting setting + 9.6 V power supply
hu1
Awaiting setting + 24 V power supply
h1
Awaiting start of auto-programming
h2
Auto-programming mode - opening
h4
Auto-programming mode - closing
F0
Awaiting remote control memorisation for operation in complete opening mode
F1
Awaiting remote control memorisation for operation in pedestrian opening mode
F2
Awaiting remote control memorisation for remote lighting control
F3
Awaiting remote control memorisation for auxiliary output control
solution?
Check that "P07" is correctly configured. Check the wiring of the cells.
Check that "P09" is correctly configured. Check the programmable safety input wiring.
Check that "P08" is correctly configured. Check the safety edge wiring.
Check that no obstacles are causing the cells or safety edge to detect.
Check that "P07", "P08" or "P09" is correctly configured in relation to the device connected to the
safety input.
Check the safety device wiring.
Check that the photoelectric cells are correctly aligned.
Check the motor wiring.
Check the wiring, then disconnect the power supply for 10 seconds.
Repeat an order. If the fault persists, contact Somfy.
N.B.: maximum accessories consumption = 1.2 A
Check the consumption of the connected accessories.
Disconnect the backup battery and connect the control box to the mains to switch it on for the
first time.
setting
compl.