Concealed-Duct Type (Us Type); Required Minimum Space For Installation And Service - Sanyo SPW-C706VH8 Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 568

■ Concealed-Duct Type (US Type)

3-23. Required Minimum Space for Installation and
Service
● This air conditioner is usually installed above the ceiling so
that the indoor unit and ducts are not visible. Only the air
intake and air outlet ports are visible from below.
● The minimum space for installation and service is shown in
the diagram. (Fig. 3-56-3)
● *H dimension means the minimum height of the unit.
● Select the *H dimension such that a downward slope of at
least 1/100 is ensured as indicated in "3-28. Installing the
Drain Pipe".
● The maintenance space marked with "
the installation box for signal output board (ACC-SG-AGB)
sold separately is used.
● The diagram shows the detailed dimensions of the indoor
unit. (Fig. 3-57-3)
10
" is required when
*
6
692
66
640 (160x4)
26
5-ø3.1(Hole)
750
824 (Suspension bolt pitch)
680
824(Suspension bolt pitch)
Min. 200
or more
Flange for air
outlet duct
* Min. 100 mm or more for bottom air intake
1 Refrigerant tubing joint (narrow tube)
2 Refrigerant tubing joint (wide tube)
3 Upper and bottom drain port (O.D.26mm)
4 Suspension lug
5 Power supply outlet (ø30)
6 Flange for air outlet duct
7 Panel cover
29
8 Electrical component box
59
9 Frame fi lter
10 Signal output board (ACC-SG-AGB : optional)
4
Water inlet
Inspection access
(450x450)
Field supply)
37
150
10-ø3.1(Hole)
5
14
132
220
9
23
* Frame Filter uninstalled
33
Electrical
component box
Inspection
access
450x450
Refrigerant tubing
Min. 650 or more
Min. 20 or more
*Min. 20 or more
2-ø3.1(Hole)
28
30
84
81
7
1
2
33
153
3
8
150
200
14
220
132
704
23
Unit: mm
Unit: mm
Ceiling
Fig. 3-56-3
Fig. 3-57-3

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Spw-c906vh8

Tabla de contenido