Electrical Diagram; Ntc Resistances - Rotex GW-20 H12 Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 263
10.2

Electrical diagram

A
Earth connection exchanger
B
Ignition hood
C
Boiler controller
E
Earth connections
Connector X4
5 -
24V=
6-7
8-9
9-10
11-12
Connector X2
2-4
~
230V
3-6
7-8
3-5-6
Connector X5
10.3

NTC resistances

NTC 12k Ohm
T [°C]
R [ohm]
T [°C]
-15
76020
15
-10
58880
20
-5
45950
25
0
36130
30
5
28600
35
10
22800
40
F
Fuse (3.15 A T)
G
Gas block + ignition module
I
Ignition/ionization pin
M
Mains electricity supply
PWM control CH-pump. (5= PWM signal (red), E=earth)
On/off room thermostat
(0.1A-24Vdc)
Outdoor sensor
(12 kOhm / 25°C)
Tank sensor (remove through-connection)
OpenTherm room thermostat
(6-7 should be open)
Mains supply 230 V (2 = L (brown), 4 = N (blue))
Electricity supply for fan (230 V, for RHOB42AAV1 only))
CH pump
(8 = L (brown), 7 = N (blue))
Three-way valve for external tank
(e.g. EK3WV1AA)
Computer interface
R [ohm]
T [°C]
R [ohm]
18300
45
5522
14770
50
4609
12000
55
3863
9805
60
3253
8055
65
2752
6653
70
2337
P1
CH pump
V
Fan
S1
Leaving water sensor
S2
Return sensor
and/or frost thermostat
(3 = L (brown), 5 = Switch (black), 6 = N (blue))
T [°C]
R [ohm]
75
1994
80
1717
85
1467
90
1266
95
1096
100
952
53

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Gw-20 h18Gw-20 h42Rhob12aav1hRhob18aav1hRhob42aav1h

Tabla de contenido