JAM PROTECTION - SLUG MODE ONLY
This feature, when enabled, helps prevent product pile-up and/or
damage if a carton should become jammed on the conveyor. The
sequence of operation when a jam occurs is as follows:
If a carton becomes jammed at any point along the conveyor for
a period of 6 seconds or longer, cartons on the upstream side of
the jammed carton will stop in sequence until the jammed carton is
dislodged or removed. The zone containing the jammed carton will
continue to drive, in many cases dislodging the jammed carton without
additional help. The accumulated zones will return to normal once the
jam is cleared.
• IOP Unit (Power Suppy for
®)
GEN3 EZLogic
The model RBE24Ez is equipped with an IOP unit (power supply.)
The IOP unit provides DC power for the EzLogic® system and
provides a wiring hub for advanced features (if I/O boards are present).
The IOP unit connects to the EzLogic® system by way of an IOP Tee Cable mounted in line
with the zone controller cordsets (see figure 6A).
Note:
See EzLogic® GEN3 Component manual and IOP Solutions manual for more
information.
EZLOGIC® ZONE CONTROLLER
FIGURE 6A
(CONTROLADOR DE ZONA DEL EZLOGIC®)
IOP
(IOP)
• Power Supply Unit for Motor
The E24™ family of conveyors is equipped with a 24 volt DC power suppy unit for providing
power to the drive card and motor combination. Each power supply provided is a high efficiency
DC power supply in a sealed industrial enclosure. (figure 6B)
The various wiring connections, adjustments and settings, and electrical specifications of the
power supply unit are described in this section.
Electrical Connections
Input power connections are made inside the enclosure. Wiring harness power
connections are made to connector on the outside of the enclosure.
AC Input
AC power for the power supply unit is connected directly to the disconnect
switch, and the ground wire is connected to the grounding terminal block.
(figure 6C and 6D)
The dual voltage single phase input powered units will automatically adjust to
the 115 VAC or the 230 VAC input power.
DC Output
Connect the wiring harness to a connector on the side of the enclosure.
NOTE: Based on higher Amp setting used, no more than 7 cards and
motors can be connected to one side of a power supply unit. When more
than 20 amps is required, you must use a 40 amp power supply unit and
make sure that no more than 20 amps is required from each side of the
power supply unit.
mount the power supply unit near the center of the conveyors and connect the
wiring harnesses to each side of the power supply.
A gender changer cable is supplied for one side of the power supply.
Main Power Disconnect Switch
The main power disconnect switch handle is located on the front door. The switch
can be used to turn the conveyor on and off to perform maintenance. It may be
"locked out" in the off position if desired/required.
EZLOGIC® ZONE CONTROLLER CORDSET
(CABLES DEL CONTROLADOR DE ZONA DEL EZLOGIC®)
IOP TEE CABLE
(CABLE TEE DEL IOP)
FIGURE 6E
DC Power
Indicator Light
Mounting Holes
(Luz Indicadora de
(Orificios de Montaje)
Potencia DC)
AC Power
Indicator Light
(Luz Indicadora de
Potencia AC)
FIGURE 6B
Left Side View
FIGURE 6C
SINGLE PHASE
CUSTOMER CONNECTION
INCOMING POWER
1PH, 100-240V ( +10%)
2.6 / 1.4 AMPS (3 AMPS INRUSH PEAK)
FIGURE 6D
THREE PHASE
CUSTOMER CONNECTION
INCOMING POWER
3PH, 380-480V (-15%, +20%)
0.9 AMPS (4 AMPS INRUSH PEAK)
6
Conduit Plugs
(Tapones del Conducto)
16"
14.5" Sub
Top of Enclosure
(Parte Superior de la Caja)
2"
6"
6"
Right Side View
(Vista Lateral Izquierda)
GND
NEU
L1
NOTE:
Terminals Seperated to
Clarify Wiring Details
GND
L3
L2
L1
NOTE:
Terminals Seperated to
Clarify Wiring Details
Output Power
Receptacle
(Salida de Potencia
Recipiente)
On/Off Switch
(Interruptor de
Encendido/Apagado)
(Vista Lateral Derecha)

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido