Hitachi KPI-502X4E Manual De Instalación Y Funcionamiento página 12

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 19
KPI UNITS INSTALLATION
Drain Pan Level

KPI-(502-1002)X4E
Make sure that the foundation is flat, taking into account the
maximum foundation gradient.
The unit should be installed so that one side of the unit is
slightly (approximately 1º (KPI-(502-1002)X4E) lower than the
other side, in order to avoid the incorrect position of the drain
discharge.
3.1.3 Connecting Field Supply Duct and Suction Air Filter Servicing

Field Supply Duct installation
The supply duct should be connected with the unit through
flexible duct, in order to avoid abnormal sounds and vibration.
The unit is equipped with a pre-drilled duct flange for the supply
duct connection.
1 Set the supplied rubber duct joint to each duct adapter to
ensure a good junction of the ducts.
2 Fit the ducts securely into the duct connecting flanges,
and wind aluminium tape available from hardware store to
prevent air leaks, also duct connection flanges have their
own sealing installed.
3 Suspend the ducts from the ceiling so that their weight will
not be applied to the unit.
4 The two outdoor ducts must be covered with heatinsulating
material in order to prevent condensation from forming.
Heat-insulating
material
Outdoor duct
Duct connecting flange
6
PMML0371A rev.1 - 08/2016
Flange
Unit
Tighten the nuts of the suspension bolts with the suspension
brackets after adjustment is completed. Special plastic paint
must be applied to the bolts and nuts in order to prevent them
from loosening.
?
N O T E
Keep the unit as well as relevant equipment covered with the vinyl cover
during installation work.
!
C A U T I O N
Before connecting the ducts, check that no sawdust or any other for-
eign matter (scraps of paper, vinyl, etc.) is inside the ducts.
Do not touch the damper plate inside the main unit when connecting
the ducts.
Do not install the ducts as shown in the next figures. Doing so, air
volume will be reduced and abnormal sounds may occur.
Extremely sharp bends
Bends right next to the outlet
Multiple bends
Extreme reduction in the
diameter of the connected
ducts

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido