BTL7-V50T-M _ _ _ _ -P-C003
Micropulse Transducer in a Profile Housing
4
Installation and connection (continued)
4.4

Electrical connection

The transducer is connected via a connector.
The pin assignments for the respective version can be
found in Table 4-3.
Note the information on shielding and cable
routing.
4.4.1
Connector BTL7-...-C003
Power
Pin
Cable color
1
BN brown
2
WH white
3
BU blue
4
BK black
BUS IN/OUT (data)
Pin
Cable color
1
YE yellow
2
WH white
3
OG orange
4
BU blue
1)
Unassigned leads can be connected to the GND on the controller side but not to the shield.
2)
Reference potential for supply voltage and EMC-GND.
Tab. 4-3:
Pin assignment of ...-C003 connector
4.5

Shielding and cable routing

Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect transducer and controller using a shielded
cable. Shielding: Braided copper shield with minimum
85% coverage.
Connector version: Shield is internally connected to
connector housing.
Magnetic fields
The position measuring system is a magnetostrictive
system. It is important to maintain adequate distance
between the transducer and strong, external magnetic
fields.
10
english
Signal
10 to 30 V DC
Not used
1)
0 V GND
2)
Not used
1)
Signal
TX+
RX+
Fig. 4-10: Pin assignment of connector (view from above on
TX−
RX−
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Cable length
The maximum cable length when using CAT5e cables is
100 m
Prerequisite: Construction, shielding and routing preclude the effect of any
1)
external noise fields.
Noise elimination
To avoid equipotential bonding - a current flow - through
the cable shield, please note the following:
Power
(pin)
3
1
4
2
1
2
2
4
3
Bus OUT/Port2
(socket)
transducer)
.
1)
Use insulating bushes
Put the control cabinet and the system in which the
BTL7 is located to the same ground potential.
3
4
1
Bus IN/Port1
(socket)