ELECTRICAL CONNECTIONS

DANGER!
Always install a general automatic switch in a
protected area near the appliance with a
characteristic delayed curve, sufficient capacity and
breaking power. There should be a minimum
distance of 3 mm between the contacts.
Earth connection is compulsory by law and
safeguards the user while the machine is in use.
DANGER!
Electrical connection of the unit must be carried out
by personnel skilled in the matter and in
compliance with the regulations in effect in the
country where the unit is installed. Non-conforming
electrical connection relieves
responsibility for damage to persons and property.
In making the electrical connections to the board,
cables must be routed so that they do not touch the
hot parts of the machine (compressor, flow pipe
and liquid line). Protect the wires from any foam.
IMPORTANT!
For electrical connections to the unit and the
accessories, follow the wiring diagrams which are
supplied with them.
The safety door interlock automatically prevents electric power being
fed to the unit if the cover panel over the electrical panel is opened.
After opening the front panel of the unit, feed the supply cables through
the appropriate cable clamps in the external panelling and then through
the cable clamps at the base of the electrical board.
The electrical power supplied by the single-phase or three-phase line,
must be taken to the main isolator switch.
The supply cable must be of the flexible type, with polychloroprene
sheathing of no lighter than H05RN-F: for the section, refer to the table
below or the wiring diagram.
117
mm
124
mm
130
mm
The earth conductor must be longer than the other conductors in order
to ensure that in the event of the cable clamping device becoming
slack, it will be the last to come under strain.
II.6.1.1
Remote management using connections set
up by the installer
The connections between board and switch or remote light must be
made with screened cable consisting of 2 twisted 0.5 mm² wires and the
screening. The screening must be connected to the earth screw on the
panel (on one side only). The maximum permitted distance is 30 m.
SCR - Remote ON/OFF control selector.
SEI -
AUTOMATIC
(Summer)/
SELECT
LBG – General lockout light.
CR – Recovery consent.
IOM_EQP1X_117a133_208094_200901_ES-EN-FR-DE-IT
HITECSA
from all
4
4
1,5
6
6
1,5
10
10
1,5
(Winter) selector
SECTION II: INSTALLATION AND MAINTENANCE
 Remote ON/OFF enablement (SCR)
IMPORTANT!
When the unit is switched OFF using the remote
control selector, the words OFF BY DIGITAL INPUT
appear on the control panel display.
Remove the ID8 terminal bridge on the electronic board and connect
the wires coming from the remote control ON/OFF selector (selector to
be installed by the installer).
Open contact:
ATTENTION
Closed contact:
 Remote
AUTOMATIC
(Summer) /
(SEI).
Connect the wires coming from the remote summer/winter selector on
the ID7 terminal present on the electronic board.
Now modify the parameter Rem. Summer/Winter (see Par. I.6.6.4).
Open contact:
ATTENTION
Closed contact:
 LBG remote control
To set up remote control of the two signals, connect the lamp according
to the instructions provided in the wiring diagram supplied with the
machine (230 Vac).
 Recovery enablement (CR).
Connect the wires coming from the remote recovery consent contact
(i.e. boiler thermostat) to terminals 7.06 – 7.07 on the terminal board.
Open contact:
ATTENTION
Closed contact:
II.6.1.2
Remote management using accessories
supplied separately
It is possible to remote control the entire machine by linking a second
keyboard to the one built into the machine (KTR accessory).
In this case, unplug the unit control panel telephone lead from the unit
electronic board housing and plug in the remote control lead in its place.
To select the remote control system, consult paragraph II.2. The use
and installation of the remote control systems are described in the
Instruction Sheets provided with the same.
II.7

START-UP INSTRUCTIONS

IMPORTANT!
Machine commissioning or the first start-up (where
provided for) must be carried out by skilled
personnel from workshops authorised by
HITECSA
, qualified to work on this type of product.
IMPORTANT!
The use and maintenance manual for the pumps is
enclosed with this manual and must be read
throughout.
DANGER!
Before starting up, make sure that the installation
and electrical connections conform with the
instructions in the wiring diagram. Also make sure
that there are no unauthorised persons in the
vicinity of the machine during the above operations.
DANGER!
The units are equipped with safety valves
positioned inside the technical compartment. When
they cut in, they cause a loud noise and violent
refrigerant and oil leaks. Do not approach the safety
valve cut-in pressure.
56
the unit is OFF.
the unit is ON.
SELECT
(Winter) enablement
heating cycle.
cooling cycle.
recovery disabled
recovery enabled