Example
Transformer-rated meters only.
A meter is connected via a 500/5 transformer. The Ct ratio 100 must be
set on the meter.
Step
Action
1
Press
S
2
Press
S
3
Press
S
4
Press
Sc
5
Press
S
6
Press
S
7
Press
LSc
Display shows
x 1
Ct 1
x 1
Ct 1
x 2
Ct – 0 0 0
x 1
Ct – 1 0 0
x 1
Ct 0 1 0 0
x 1
Ct 100
Normal mode
To set mode.
Activates set mode, hand
starts to blink.
Accepts 0 as the value of
the two last digits.
Activates the second digit.
Increases the value of the
second digit by 1.
Activates the first digit.
Accepts the Ct ratio 100.
Back to normal mode.
50