Description; Bbpr (Gs6) Models - VALPES VRX Manual De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

BBPR (GS6) : description
Actuators with emergency unit (on-off wiring mandatory)
The BBPR models include an emergency battery unit controled by an electronic board. This system insure a return to predefi-
ned position in case of power failure. The predefined position can be set close (default) or open.
The BBPR actuators can be only on-off mode wired.
The factory default configuration is "normally closed"
Actuator voltage
Battery voltage
Battery capacity
Charging current
battery charge maximum duration
Following a power failure,
the BBPR unit will reset
after 4 minutes
REP TERMINAL DESCRIPTION
17 (-)
C1
power supply connector
18 (+)
F (+)
C2
F (-)
Battery unit connector
T (+)
A
C3
B
Motor connector
C
D3
C4
1)
Failure feedback connector
D4
65
C5
1)
Charging feedback connector
66
A
C6
0
RS485 connector
B
J1
Bluetooth
activation jumper
®
1) The auxiliary cables must be connected to inside instal-
lation only
48
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
20 V to 30 V AC 50/60 Hz and 20 V to 48 V DC
24 V DC
Charging status feedback relay (65/66)
600 mAh
Failure feedback relay (D3/D4)
180 mA
Temperature
3,5 h
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 06 ATEX 6006X
Ambient temperature: -10 °C to +40 °C
C1
C2
C3
LED
ACT
ERROR
HORO
MANU
WIRE
J1

DESCRIPTION

Power supply:

Slow blinking (1 s) : charged battery

Rapid blinking (0.5 s) : battery charging
Error detected:

Timestamp memory empty/scheduler selected

Clock failure

Excessive temperature

Excessive torque
Weekly scheduler functioning mode
manual / Bluetooth
functioning mode
®
Electric wiring mode
DSBA3401
EN
24 V DC - 1 A max
24 V DC - 3 A max
-10 °C to +40 °C
LED
C6
C5
C4
Rév. 08/08/2020
·