PFW03-M12_24
Especificación técnica
Supply
Voltage.............95..410V AC +_ 10%
Frequency........45-65 Hz
Measurement Inputs
Voltage..... ......95..410V AC +_ 10% (L-N)
......................95..410V AC +_ 10% (L-L)
Current............. 0.01..6 A RMS
Frequency........ 45..65 Hz
Night/Day Input. 95.. 240 VAC RMS
Relay Outputs for Compensation
12/24 pcs.,
Max. switching voltage... : 250 VAC
Max. switchig current..... : 2A
Alarm Relay Outputs:
2 pcs,
Max. switching current.....: 4A
Max. switching voltage....: 250 VAC
Max. switching power...... : 1250 VA
Protection class
IP40 front, IP20 rear