Diagrama de Cableado de Sistema AC (36/48K 3 fase)
OFM
BLUE
IFM
PURPLE(COM)
IFM BLOWER MOTOR TAP
NOTES:
1: Remove the red lead from
240V
terminal and then connect the red lead to
2: Exchange the indoor blower motor red wire and blue wire for medium speed ;exchange the blower motor black wire and blue wire for high speed; default as low speed of factory settings.
3:
W2
wire is not provided in some models and
B
is only for HP unit .
4:
MANUAL DEFROST
and
JUMP
is unavailable for AC unit.
PLUG PLATE
T1
T2
WHITE
T3
CC
CN17
C
Y-OUT
LED1
O FAN
CN6
TDC
CN13
CN7
RED(M)
JUMP
CN10
0
BLUE(L
)
INFAN
0
MANUAL DEFROST
T4
RV
C
T
208V
terminal on the transformer for 208 volts.
GND
L1
L2
R
C
WHITE
D
GREEN
G
YELLOW
Y
BLUE
B
WHITE/BLACK
W2
6
1
5
1
4
3
2
1
CC
COMPRESSOR CONTACTOR
COMP
COMPRESSOR
TDC
TIME DELAY CONTROL
T4
10K RESISTANCE.
T3
10K RESISTANCE.
OFM
OUTDOOR FAN MOTOR
RC 2
OUTDOOR FAN MOTOR RUN CAPACITOR
RC 3
INDOOR FAN MOTOR RUN CAPACITOR
GND
GROUND CHASSIS
IFM
INDOOR FAN MOTOR
LINE VOLTAGE
FACTORY STANDARD
FIELD INSTALLED
FACTORY OPTIONAL
LOW VOLTAGE
FACTORY STANDARD
FIELD INSTALLED
FACTORY OPTIONAL
USE COPPER CONDUCTORS ONLY
WARNING
CABINET MUST BE PERMANENTLY
GROUNDED AND ALL WIRING TO CONFORM TO
I.E.C, N.E.C, C.E.C, C.L.C, AND LOCAL CODES AS APPLICABLE
REPLACEMENT WIRE MUST BE THE SAME GAUGE AND
INSULATION TYPE AS ORIGINAL WIRE.
STEADY ON = NORMAL OPERATION
0
OFF =TDC FAILURE
1 FLASH = T3 SENSOR FAILURE
1
2 FLASH = T4 SENSOR FAILURE / HPC OR HGS OPEN
2
3 FLASH = LPC OPEN
3
4 FLASH = POWER PHASE FAILURE
4