Ordering Codes

S 9 2 10 - B D C- 31 A 2-POINT actuator with 2 auxiliary
switches
-
=
no sensors
A
=
with ambient thermosensor
B
=
with duct sensor
C
=
with duct and ambient sensor
31
=
10 mm Couppler
32
=
11 mm Couppler
33
=
12 mm Couppler
34
=
14 mm Couppler
D
=
230 VAC
G
=
24 V AC/DC
10
=
10 Nm
20
=
20 Nm

Technical Specifications

Product Codes
Power Requirements
Power Requirements
- Running
- Holding Position
- Running
- Holding Position
Transformer Sizing Requirements
- Minimum per Actuator
Input Signal / Adjustments
Auxiliary Switch Rating
Spring Return
Running and Spring Return Torque
Rotation Range
Rotation Time
- Power On (Running
- Power Off (Spring Returning)
Cycles
Audible Noise Rating
- Power On (Running)
- Power On (Holding)
- Power Off (Spring Returning)
Electrical Connections
(Actuator and Auxiliary Switches)
Conduit Connections
Mechanical Connections
- Standard Shaft Clamp Available
Aluminum Enclosure
Ambient Conditions
- Operating
- Storage
Shipping Weight
Dimensions
Conformity
2
S9210-BxC / S9220-BxC
S9210-BGC-xxx
AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz
Class 2 (North America) or SELV (Europa)
26 VA
9.3 VA
DC 24 V (DC 21.6 to 26.4 V), Class 2 (North America) or SELV (Europe)
15.6 W
2.6 W
25 VA
---
Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with Gold Flash Contacts:
AC 24 V, 50 VA Pilot Duty;
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty;
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Direction is Selectable with Mounting Position of Actuator:
Side A, Actuator Face Away from Damper for CCW Spring Return;
Side B, Actuator Face Away from Damper for CW Spring Return
10 Nm
Optional
M9210-603 Adjustable Stop Kit
24 to 57 Seconds for 0 to 10 Nm
at All Operating Conditions
11 to 15 Seconds for 0 to 10 Nm
at Room Temperature
35 Seconds maximum
for 0 to 10 Nm at -30° C
130 Seconds maximum
for 0 to 10 Nm at -40° C
60,000 Full Stroke Cycles; 1,500,000 repositions
<66 dBA at 1 m
<18 dBA at 1 m
<66 dBA at 1 m
1.2 m Halogen-Free Cable with 18 AWG (0.75 mm
2
) Wire Leads
Integral Connectors for 10 mm Flexible Metal Conduit
10, 11, 12, and 14 mm Square Shafts
NEMA 2 (IP54) for All Mounting Orientations
-40 to 55° C; 90% RH Maximum, Noncondensing
-65 to 85° C; 95% RH Maximum, Noncondensing
2.9 kg
See Figure 1
EMC Directive 2004/108/EC
Low Voltage Directive 2006/95/EC
S9220-BGC-xxx
ON/OFF
17.6 W
2.8 W
---
---
20 Nm for a Single Actuator
Optional
M9220-603 Adjustable Stop Kit
M9210-603 Adjustable Stop Kit
Adjustable from 30 to 90° CW or CCW Mechanically Limited to 90°
24 to 57 Seconds for 0 to 20 Nm
24 to 57 Seconds for 0 to 10 Nm
at All Operating Conditions
at All Operating Conditions
35 Seconds Nominal at Full Rated Load
11 to 15 Seconds for 0 to 20 Nm
11 to 15 Seconds for 0 to 10 Nm
at Room Temperature
35 Seconds maximum
for 0 to 20 Nm at -30° C
130 Seconds maximum
for 0 to 20 Nm at -40° C
S9210-BDC-xxx
S9220-BDC-xxx
AC 230 V (AC 198 to 264 V) at 50/60 Hz
0.12 A
0.09 A
---
---
---
25 VA
---
10 Nm
20 Nm for a Single Actuator
Optional
M9220-603 Adjustable Stop Kit
24 to 57 Seconds for 0 to 20 Nm
at All Operating Conditions
11 to 15 Seconds for 0 to 20 Nm
at Room Temperature
at Room Temperature
35 Seconds maximum
35 Seconds maximum
for 0 to 10 Nm at -30° C
for 0 to 20 Nm at -30° C
130 Seconds maximum
130 Seconds maximum
for 0 to 10 Nm at -40° C
for 0 to 20 Nm at -40° C
3.5 Kg
0.15 A
---
---
Optional