Combustion Head Adjustment; Combustion Air Adjustment - Lamborghini Caloreclima ECO 14/2 Manual Para La Instalación Y El Mantenimiento

Quemadores para gasóleo
Ocultar thumbs Ver también para ECO 14/2:
Tabla de contenido

Publicidad

COMBUSTION HEAD ADJUSTMENT

Combustion head adjustment is to be made by operating on screw (A).
By turning this screw, diffuser position is changed into the draught tube which causes change in the air
passage section.
Reference index (B)
1
Minimum delivery
Medium delivery
2
3
Maximum delivery

COMBUSTION AIR ADJUSTMENT

Air shutter is operated by the motor-reducer;
close/open and 1st stage/open max. adjustments
are to be made on the cams, by turning anti-
clockwise to increase air shutter opening and
clockwise to decrease it.
Cam II Total closing position
Cam III 1st stage starting adjustment
Cam I 2nd stage starting adjustment
Cam V 2nd stage VE2 opening ok (must be
adjusted to at least 6° more than cam III.
Setting
range
HONEYWELL MT 4002B 1008
17

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Eco 22/2

Tabla de contenido