ELECTRICAL WORK
For the air conditioner that has no power wire,
connect a power wire as mentioned below.
Model
Power supply
Maximum running current
Installation fuse rating
Power wire
CAUTION
• Wrong wiring may cause a burnout to some
electrical parts.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core
and inner insulator of power and inter-connect-
ing wires when peeling them.
• Be sure to comply with local regulations of the
wire from outdoor unit to indoor unit.
(wire size and wiring method etc.)
• Use the power and Inter-connecting wires with
specified thickness, specified type and protec-
tive devices required.
How to remove the valve cover
1. Remove screws of the valve cover.
2. Pull the valve cover downward to remove it.
Piping cover
Indoor/outdoor
connecting cables
Power cable
RAV-SM56, RAV-SM80
220 – 240 V
Single phase 50 Hz
15 A
16 A (all types can be used)
H07 RN-F or 60245 IEC 66
2
(1.5 mm
or more)
Valve cover
How to wire
1. Connect the connecting wire to the terminal as
identified with their respective numbers on the
terminal block of indoor and outdoor unit.
H07 RN-F or 60245 IEC 66 (1.5 mm
2. When connecting the connecting wire to the
outdoor unit terminal, prevent water coming in the
outdoor unit.
3. Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that
they do not touch any electrical or metal parts.
4. For inter connecting wire, do not use a wire jointed
to another on the way.
Use wires long enough to cover the entire length.
Screw
Connecting wire
Tripping length power cord and connecting wire
10
1 2 3
40
Earth line
Connecting
wire
• The installation fuse must be used for the power
supply line of this air conditioner.
• Incorrect/incomplete wiring might cause an
electrical fire or smoke.
• Prepare the exclusive power supply for the air
conditioner.
• This product can be connected to the mains.
Connection to the fixed wiring :
A switch which disconnects all poles and has
a contact separation of at least 3 mm must be
incorporated in the fixed wiring.
11
2
or more)
Terminal block
1
2
3
L
N
Power wire
L N
10
10
30
30
(mm)
Power wire
CAUTION
10
40
Earth line