WEG CFW500 Guía De Instalación, Configuración Y Operación página 7

Módulo plug-in de expansión de i/o de analógicas y digitales
Ocultar thumbs Ver también para CFW500:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Connector
1
DI1
3
DI2
5
DI3
7
DI4
9
+24 V
11
DO1-RL-NO
13
DO1-RL-C
15
DO1-RL-NC
17
AI2
19
AI3
21
DI5
23
DI6
2
AO1
4
GND
6
AI1
8
+10 V
10
DO2-TR
12
RS485 - A
14
RS485 - B
16
GND
18
GND
20
AO2
22
DO3-TR
24
DO4-TR
Figure 1: Signals of control connections
The location of the DIP-switches for selecting the type of
analog input and output signal and network termination
RS485 is shown in
and / or outputs with signal current, the switches S1
and S2 and related parameters must be set as shown
in
table
1. For more details on control connections
refer to chapter 3 - Installation and Connection of the
CFW500 user manual.
Analog and Digital I/O Plug-in Module
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Power suply +24Vdc
Digital output 1
(relay 1 NO contact)
Digital output 1
(common point of relay 1)
Digital output 1
(relay 1 NC contact)
Analog input 2
Analog input 3
Digital input 5
Digital input 6
Analog output 1
Reference 0 V
Analog input 1
Reference +10 Vdc for potenciometer
Digital output 2 (transistor)
RS485 (terminal A)
RS485 (terminal B)
Reference 0 V
Reference 0 V
Analog output 2
Digital output 3 (transistor)
Digital output 4 (transistor)
figure
A.2. To use the analog input
Description
CFW500 | 7