1
3
Press the test switch or disarm the system at the controller.
To silence the detector:
The detector sounds again after 5 minutes if the alarm
condition continues. When programmed in one-go-all-go
mode, the detector can only be silenced from the controller.
Para silenciar el detector:
Presione el interruptor de prueba o desarme el sistema
desde el controlador. El detector volverá a sonar después
de 5 minutos si continúa la condición que originó la alarma.
Cuando está programado en el modo activa-uno-activan-
todos, el detector solo se podrá silenciar desde el
controlador.
Duracell or Panasonic CR123A
Replace Battery / Cambiar bacteria
Approval Listings / Listas de aprobaciones:
FCC / IC
ETL Listed to UL268, UL 521 & UL 2075.
cETL Listed to ULC-S530, ULC-S531 & CSA
Other Standards: RoHS
NOTE: Smoke detectors are not to be used with detector guards unless the
combination is evaluated and found suitable for that purpose.
NOTA: Los detectores de humo no se deben usar con protecciones de detector a
menos que la combinación se haya evaluado y comprobado que es adecuada para
ese propósito.
© 2016 Honeywell International Inc. Honeywell and is a registered trademark of Honeywell International Inc.
All other trademarks are the properties of their respective owners. All rights reserved
www.honeywell.com/security
2
4
Maintenance
0
~ 10
10
45
sec / seg
20
30
6.19.
Specifications / Especificaciones:
Battery / Batería: 4 x 3V, CR123A Lithium; Panasonic or Duracell only
Sensitivity: UL limits .9 to 2.84%/ft / ULC limits .9 to 2.64 %/ft
Audible Signal: 85dBA
Dimensions / Dimensiones:
13.46 cm Diameter x 4.19 cm Thick / 6.3 in. Diameter x 1.65 in. Thick
Tamper / Tamper: Cover
Operating Temperature / Temperatura de funcionamiento: 32° – 122° F / 0° – 50° C
Storage Temperature: -10° -70° C (14-158° F)
Relative Humidity / Humedad relativa:
20-95% RH (Agency Compliance – 93% max.), non-condensing
NOTE: Batteries available at your local retailer or distribution center.
NOTA : Las baterías están disponibles en los distribuidores locales.
FEDERAL COMMUNICATIONS COMMISSION & INDUSTRY CANADA
STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the
Installation Instructions or User's Manual. Unauthorized changes or modifications could void the
user's authority to operate the equipment.
FCC / IC STATEMENT This device complies with Part 15 of the FCC Rules, and RSS-210 of
Industry Canada. Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) This device must accept any interference received, including
interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS-210 des Industries
Canada. Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas
causer d'interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y compris
les interférences causant une réception indésirable.
RF EXPOSURE WARNING – The antenna(s) used for this device must be installed to provide
a separation distance of at least 7.8 inches (20 cm) from all persons and must not be co-located
or operating in conjunction with any other antenna or transmitter except in accordance with FCC
multi-transmitter product procedures.
MISE EN GARDE EXPOSITION AUX FREQUENCES RADIO: L'antenne (s) utilisée pour cet
émetteur doit être installée à une distance de séparation d'au moins 7,8 pouces (20 cm) de
toutes les personnes.
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED,
FOR DETAILS REGARDING LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
CONSULTE LAS INSTRUCCIONES DE INSTALACIÓN PARA EL CONTROL CON EL CUAL SE UTILIZA ESTE
DISPOSITIVO, PARA OBTENER DETALLES CON RESPECTO A LAS LIMITACIONES DE TODO EL SISTEMA DE
ALARMA.
Product must be tested at least once each year / El producto debe ser probado al menos
una vez al año
Support / Soutien
https://mywebtech.honeywell.com/
U.S. warranty / U.S. garantie
www.honeywell.com/security/hsc/resources/wa
For patent information, see:
Para información de Patentes, vea :
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
MyWebTech
www.honeywell.com/patents
Patents
800-22195 9/16 Rev A