SAUNA ROCKS
The rocks are cleaned at the factory, but we recommend you to hose them down once more
before placing them in the heater. The biggest rocks should be placed at the bottom and the
smallest at the top. You must not put the rocks too close as the air must circulate through the
heater. The rocks must, however, fully cover the heating elements. Please replace the rocks
after 2- 4 years.
If you do not follow the instructions above there is a risk of fire.
REGULATION
Turn the thermostat knob (fig. 4) to the temperature desired. The desired temperature will be
reached within 30- 60 minutes depending on the size, construction and isolation of the sauna.
THERMAL CUT-OFF
If the temperature in the sauna for some reason gets too high, the thermal cut-off switches off
the heater completely. After cooling down the sauna to the normal temperature you can reset
the heater by pushing the reset button (see fig. 4) on the thermal cut-off. Try, however, first to
find the reason for the sudden increase in temperature.
TIMER
The timer, which also works as a main switch , automatically switches off the heater after the
desired time . You can choose any time between 1- 6 hours. When turning the timer knob
clockwise to position 3 the heater starts to warm the sauna room and after 3 hours the heater is
automatically switched off. The timer can be turned to 0-position from all positions. If the bathing
time is shorter than expected the heater can be manually switched off by turning the knob to the
0-position. If your sauna heater has an 8 +4 hour timer, then you have 4 h of heating time and 8
hours of pre-setting time. This means that during the pre-set time only the timer will work and when
the pre-set time has is finished the 4 h heating time starts. You can also use the only the 4 h heating
time to heat the sauna up right away.
Recommended sauna room ventilation
5
4
6
2
1. Sauna room
3. Electric sauna heater
2. Washroom
4. Exhaust valve
7. A ventilation valve can be installed here to be kept closed while the sauna is heated and during bathing.
Inlet vent can be positioned in the A zone. Make sure the incoming fresh air will not interfere with (i.e. cool down) the
sauna heater's thermostat near the ceiling.
The B zone serves as the incoming air zone, if the sauna room isn't fitted with forced ventilation. In this case, the
exhaust valve is installed min 1m higher than the inlet valve.
DO NOT ISTALL INLET VALVE WITHIN ZONE C, IF THE SAUNA HEATER'S CONTROL THERMOSTAT IS
LOCATED AT THE SAME ZONE.
5
7
1
1
4
C
C
C
C
1000 mm
B
B
3
3
5. Exhaust flue or channel
6. Door to the sauna room
A
A
A
min
500 mm
1
2