BURNER OPERATION

BURNER START-UP (A)
0 s : The control box starting cycle begins.
2 s : Fan motor starts.
• 43 s : Ignition electrode strikes a spark.
• 45 s : The spark goes out.
• 53 s : The 2
STEADY STATE OPERATION (A)
At the end of the starting cycle, the control box
Red
continues to check that the flame is present and
that the air pressure switch is in the correct posi-
tion.
The burner continues to operate at constant out-
D3024
put.
If the temperature or pressure in the boiler con-
tinues to rise, and opens load control TL, the
burner will stop, section F-G.
FIRING FAILURE (B)
If the burner does not fire, it goes into lockout
within 3 s of the opening of the gas solenoid
valve and 49 s after the closing of control
device TL.
The red led of the control box comes on.
UNDESIRED SHUTDOWN DURING OPERA-
TION
If the flame should accidentally go out during
operation, the burner will lock out within 1s.
D3025
14
Control device TL closes.
After about 3s:
The air gate valve is set on maximum
adjustment output.
The pre-purge stage follows.
st
Safety valve VS and the 1
VR1 of the adjustment valve VR
open. The shutter of valve VR1 has a
first rapid run that determines a low
output firing, point A, which is fol-
lowed by a slow run. The output
increases progressively up to a 1
stage value, section A-B.
nd
stage VR2 of valve VR opens
and the output passes slowly from the
st
1
stage to the maximum adjustment
valve, section C-D.
The control value box starting cycle
ends.