7.2.2) Level one programming (ON-OFF functions).
Level 1 functions are all factory set to "OFF". However, they can be changed at any time as shown in Table 13. Follow the procedure carefully, as there
is a maximum time of 10 seconds between pressing one key and another. If a longer period of time lapses, the procedure will finish automatically and
memorize the modifications made up to that stage.
Table 13: changing ON-OFF functions
1.
Press the key [Set] and hold it down (approx. 3 s)
2.
Release the [Set] key when L1 LED starts flashing
3.
Press keys [▲] or [▼] to move the flashing LED onto the LED representing the function which is
to be changed.
4.
Press the [Set] key to change the state of the function (short flashing = OFF; long flashing = ON)
5.
Wait 10 seconds before leaving the programme to allow the maximum time to lapse.
Note: Points 3 and 4 can be repeated during the same programming phases in order to set other functions to ON or OFF.
7.2.3 Level two functions (adjustable parameters)
Table 14: programmable function list: level two
Input LED
Parameter
Pause Time
L1
Step-by-step
L2
Function
Motor speed
L3
Open Gate
Indicator
L4
Output
Motor force
L5
Open
L6
Partially
Note: "
" represents the factory setting.
LED (level)
L1
5 seconds
L2
15 seconds
L3
30 seconds
L4
45 seconds
L5
60 seconds
L6
80 seconds
L1
Open – stop – close - stop
L2
Open – stop – close - close
L3
Open – close – open - close
L4
Condominium operation
L5
Close
L6
Man present
L1
Very slow
L2
Slow
L3
Medium
L4
Fast
L5
Very fast
L6
Extremely Fast
L1
Open Gate Indicator Function
L2
On if the leaf is close
L3
On if the leaf is open
L4
Active with 2nd radio command
L5
Active with 3rd radio command
L6
Active with 4th radio command
L1
"Very light" gate
L2
"Light" gate
L3
"Average" gate
L4
"Average-heavy" gate
L5
"Heavy" gate
L6
"Very heavy" gate
L1
0,5 m
L2
1 m
L3
1,5 m
L4
2 m
L5
2,5 m
L6
3 m
value
Adjusts the pause time, namely the time
which lapses before automatic closure.
This will only have an effect if automatic
closing is active.
Manages the sequence of controls asso-
ciated to the Step-by-Step input or to the
1st radio command (see tables 4 and 5).
Adjusts the speed of the motor during nor-
mal travel.
Adjusts the function associated with the
S.C.A. output.
Adjusts the system which controls the
motor force in order to adapt it to the wei-
ght of the gate.
Adjusts the measurement of the partial ope-
ning. Partial opening can only be controlled
using the 2nd radio control (see Tables 4
and 5)
Example
SET
3s
L1
SET
o
SET
10s
Description
13