Configuration - BFT MOOVI 30S Instrucciones De Uso Y De Instalacion

Ocultar thumbs Ver también para MOOVI 30S:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 39
ENGLISH
overloads and short circuits, suitable for cutting out automation
from the mains. Place, if not al ready installed, a type-approved
differential switch with a 0.03A threshold just before the automa-
tion system.
QR)
Control panel and incorporated receiver.
S)
Key selector.
AL)
Blinker with tuned antenna.
M)
Actuators.
A)
Bar.
F)
Rest fork.
CS)
Electric edge.
CC)
Edge control.
Ft,Fr) Pair of photocells.
CF)
Photocell post.
T)
1-2-4 channel transmitter.
RMM) Inductive metal mass detector.
LOOP) Mass detector loops.
8) LEO-MV-D CONTROL PANEL
Power supply: ............................................................ 220-230V 50/60Hz
Mains/low voltage insulation: .................................... > 2MOhm 500V
Dielectric strength: .................... mains/low voltage 3750V~ for 1 minute
Motor output current: ................................................................ 1.5Amax
Maximum motor power: ................................................................. 750W
Supply to accessories: .................................. 24V~ (1A max absorption)
Gate-open warning light: ........................................ 220-230V~ 3W max
Blinker: .................................................................. 220-230V~ 40W max
Dimensions: ....................................................................... see figure 14
Fuses:..................................................................................see figure 15
9) TERMINAL BOARD CONNECTIONS (Fig.16)
WARNING – During the wiring and installation operations, refer to the
current standards as well as principles of good technical practice.
The cables must be tied by additional fastening next to the terminals, by
means of clips for example.
All the operator wiring operations must be carried out by qualified personnel.
JP1
GND terminal
1
2-3
Single-phase mains supply 220-230V 50/60Hz (2=N) (3=L)
JP2
4-5
Blinker connection (mains voltage) 40W Max.
6-7-8-9
Motor connection:
6 operation 1 + capacitor
7 common
(blue)
8 operation 2
9 capacitor
JP3
10-11
Output 24V~ 1A max – power supply for photocells or other
devices.
12-13
Gate-open warning light output (24V 3W max)
JP4
Barrier status output
20-18
Closed Contact with barrier raised
20-19
Closed Contact with barrier lowered
Contact switching for barrier status control.
To be used in Parky systems.
JP5
Encoder connection
WARNING! The maximum length of the connection cable of
the encoder should not exceed 3.00 mt.
JP8
21-22
Open-Close button (N.O. Start), key selector.
21-23
Block button (N.C. Stop). If not used, leave jumped.
21-24
Photocell input (N.C.). If not used, leave jumped.
21-25
Opening limit switch connection (N.C. SWO). If not used,
leave jumped.
21-26
Closing limit switch connection (N.C. SWC). If not used, leave
jumped.
21-27
Not used
21-28
Open-Button connection (N.O. Open)
21-29
Close-Button connection (N.O. Close)
21-30
Rubber edge connection (N.C.). If not used, leave jumped.
21-31
Connection of clock input (N.O.). If the contact connected is
open, the barrier closes and gets ready for normal operation.
If the contact is closed (N.C.), the barrier opens and remains
open until contact opening.
JP9
32
Photocell check input (PHOT FAULT) (see Fig. 16)
33
Electric edge check input (EDGE FAULT) (see Fig. 16)
38-39
Antenna input for radio-receiver (38 signal - 39 braid). Cable
RG58.
18
- MOOVI 30S-30RMM-60RMM Ver. 01
INSTALLATION MANUAL
10) PROGRAMMING
The control panel provided with a microprocessor is supplied with func-
tion parameters preset by the manufacturer, suitable for standard instal-
lations. The predefined parameters can be altered by means of either
the incorporated display programmer or Universal palmtop programmer.
In the case where programming is carried out by means of Universal palmtop
programmer, carefully read the instructions relating to Universal palmtop
programmer, and proceed in the following way.
Connect the Universal palmtop programmer to the control unit through the
UNIFLAT accessory (See fig. 17). Enter the "CONTROL UNITS" menu,
and the "PARAMETERS" submenu, then scroll the display screenfuls us-
ing the up/down arrows, and set the numerical values of the parameters
listed below.
For the function logics, refer to the "LOGIC" submenu.
In the case where programming is carried out by means of the incorporated
programmer, refer to Fig. A and B and to the "configuration" paragraph.

11) CONFIGURATION

The display programmer is used to set all the LEO MV D control panel
functions.
The programmer is provided with three pushbuttons for menu scrolling
and function parameter configurations:
+
menu scrolling/value increment key
-
menu scrolling/value reduction key
OK
Enter (confirm) key
The simultaneous pressure of the + and – keys is used to exit the active
menu and move to the preceding menu.
If the + and – keys are pressed simultaneously at the main menu level
(parameters, logics, radio, language, autosetting), programming is exited
and the display is switched off (the OK message is displayed).
The modifications made are only set if the OK key is subsequently pressed.
When the OK key is pressed for the first time, the programming mode
is entered.
The following pieces of information appear on the display at first:
- Control unit Software version
- Number of total manoeuvres carried out (the value is expressed in
thousands, therefore the display constantly shows 0000 during the
first thousand manoeuvres)
- Number of manoeuvres carried out since the latest maintenance
operation (the value is expressed in thousands, therefore the display
constantly shows 0000 during the first thousand manoeuvres)
- Number of memorised radio control devices.
When the OK key is pressed during the initial presentation phase, the
first menu (parameters) can be accessed directly.
Here follows a list of the main menus and the respective submenus available.
The predefined parameter is shown between square brackets [ 0 ].
The writing appearing on the display is indicated between round brackets.
Refer to Figures A and B for the control unit configuration procedure.
11.1) Parameter Menu (PARAM)
1 - Automatic Closing Time (TCA) [ 10s ]
Set the numerical value of the automatic closing time from 1 to 180
seconds.
2 - Slow-down Distance (Cm. rall) [ 5 ]
Set the required slow-down distance for opening and closing between
1 and 90.
NOTE: power failure, reset, or manual gate release, the control panel
carries out a complete manoeuvre at reduced speed, in order to learn
the length of stroke.
3- Alarm time (alarm. time) [ 30s ]
In the case of obstacle detection or photocell engagement, at the end
of the time set (ranging from 10s to 240s) the SCA contact is closed.
The contact is subsequently opened by the STOP command or by
triggering of the closing limit switch. Only active when the SCA Alarm
logic is set to OFF.
4- Zone (zone) [ 0 ]
Set the zone number between a minimum value of 0 and a maximum
value of 128. See paragraph 8 on "Serial connection".
5- Slow-down torque (slud torque ) [ 99% ]
Set the motor torque value during the slow-down phase between 0%
and 99%.
6- Opening torque (open torque) [ 70% ]
Set the motor opening torque value between 1% and 99%.
7- Closing torque (cls. torque) [ 70% ]
Set the motor closing torque value between 1% and 99%.
8 - Brake (Brake) [ 52% ]
Set the required brake value between 0 and 99%, compatibly with the
weight of the rod and the existing stresses.
9 - Encoder (Encoder) [ 1 ]
0: encoder disabled: timed slow-down, obstacle detection function
not active. (The encoder can be disconnected).
1: encoder enabled: slow-down and obstacle detection by means of