Ideal 61-795 Manual De Instrucciones página 9

Ocultar thumbs Ver también para 61-795:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Ranges & Accuracies
AC Converter: 61-795 model is averaging sensing, rms calibrated
Accuracy: Accuracy is specified as +/-(a percentage of the reading + a fixed
amount) at 23°C±5°C (73.4°F ± 9°F), less than 75% relative humidity.
Temperature Coefficient: 0.1 times the applicable accuracy specification
from 32°F to 64°F and 82°F to 122°F (0°C to 18°C ; 28°C to 50°C).
Function
DC Voltage
AC Voltage
Resistance
Continuity*
Insulation
Resistance**
250V
500V
1000V
*Continuity test current > 200mA @ R<5Ω and open circuit voltage (4-24VDC)
per EN 61557-2/VDE 0413 Part 4.
**Auto Ranging. Open circuit voltage: <1.3 x V
0% to +10%. Short circuit current: <3.0mA. Nominal testing current: 1mA @
1kΩ x V (1mA @ 500kΩ)
Range
0.1 - 600.0V
0.1 - 600.0V
0.1 - 199.9Ω
0.01 - 19.99Ω
0.001 - 0.100MΩ
0.101 - 3.999MΩ
4.00 - 39.99MΩ
40.0 - 399.9MΩ
400 - 1000MΩ
0.001 - 0.250MΩ
0.251 - 3.999MΩ
4.00 - 39.99MΩ
40.0 - 399.9MΩ
400 - 2000MΩ
0.001 - 0.250MΩ
0.251 - 3.999MΩ
4.00 - 39.99MΩ
40.0 - 399.9MΩ
400 - 1000MΩ
1000 - 4000MΩ
Accuracy
±(0.5% +1)
±(0.8% + 4)
±(2.0% + 3)
±(2.0% + 3)
±10
±(2.0% +5)
±(5.0% +5)
±15
±(2.0% +5)
±(5.0% +5)
±15
±(2.0% +5)
±(3.0% +5)
±(5.0% +10)
.
Accuracy of nominal voltage:
0
9
Overload
Protection
600V AC RMS max
600V AC RMS max
600V AC RMS max
for 1 minute
600V RMS max
600V RMS max

Publicidad

Tabla de contenido
loading

Tabla de contenido