DRYING TUMBLER ENCLOSURE CONSTRUCTION

FACILITIES REQUIRED

IMPORTANT: DO NOT block the airflow at the rear
of the tumbler with laundry or other articles. Doing
so would prevent adequate air supply to the
combustion chamber of the tumbler.
A typical tumbler enclosure is shown in Figure 2 Note
that the enclosure touches the tumbler top and side
panels. Also, note the minimum and maximum
dimensions. Be aware that there may be local codes and
ordinances which must be complied with.
To reduce the risk of severe injury, clearance of tumbler cabinet from combustible
construction must conform to the minimum clearances.
NOTE: Shaded areas
indicate adjacent
structure.
Top
First 4" (10.2 cm)
0" (0.0 cm)
To assure compliance, consult local building code
requirements.
70369801
WARNING
0" CLEARANCE PERMITTED
FOR FIRST 4" (10.16 cm)
0" CLEARANCE
Minimum Recommended Clearances
Top
(Remainder)
12" (30.5 cm)
Figure 2
To reduce the risk of serious injury, install
lockable door(s) to prevent public access
to rear of tumblers.
IMPORTANT: Install tumblers with sufficient
clearance for servicing and operation. Refer to
Figure 2.
4" (10.16 cm)
MAXIMUM
24" (61 cm) MINIMUM
36" (91.4 cm) RECOMMENDED
FOR MAINTENANCE PURPOSES
Back
24" (61 cm)
A drying tumbler produces combustible
lint. To reduce the risk of fire, the tumbler
must be exhausted to the outdoors.
WARNING
12" (30.5 cm)
MINIMUM
CLEARANCE
PERMITTED
FOR REMAINDER
GUARD
PROVISION
FOR
MAKE-UP
AIR
T038IE3D
Sides
0" (0 cm)
WARNING
W055
W056
W057
19