Measuring Single-Phase Circuit
(Figure 8. Single-phase Power
Measurements)
2
AC
PF
MEM
0 0
20
40
60
1.
Hook the clamp jaws around the
conductor of the loading or the
circuit. The clamped conductor
is one phase which you want to
test in the three-phase circuit.
2.
Turn the selector to one of
Φ1,Φ2,Φ3, and refer to Table 3
to connect test leads into input
terminals which is corresponding
to the position of the selector. (
Figure 8)
3.
After right connection, you can
measure five power parameters
of single-phase circuit (Active
Power, Power Factor, Apparent
Power, Reactive Power, Active
Energy):
www.grupotemper.com
Phase digital power clamp meter
MAX
1000A
600kW
OFF
EX
-
P
MR
W
3
2
Ture RMS
AUTO RANGE
1
OFF
kVA
kWh
kW / PF
kVAr
TIME
V / Hz
A
RS232
kW
2
AC
PF
MEM
0 0
20
40
60
MAX
MIN
80
100
V1
V2
V3
KP 2203
Tested conductor
MAX
600V
CAT.I
II
Earth wire
HOLD
CLEAR
kW
80
100
SAVE
COM
Black
Green
( 1. ) Active Power(kW) and
Power Factor (PF) (Figure 8)
a. Press
button, the
kW / PF
Active Power value is shown
in the primary display and the
Power Factor value, "PF"
symbol are shown in the
secondary display. When the
Power Factor value is negative,
the loading is capacitive.
b. The maximum measurement
range of Active Power is
600kW. For exceeding the
maximum value, the "OL"
symbol will be shown in the
display. If test voltage exceeds
600V or the test current
Instructions manual |
45