General Information
2.2 — Protection Systems
The generator may have to run for long periods of time
with no operator present to monitor the engine/generator
conditions. Therefore, the generator is equipped with a
number of systems to automatically shut down the unit to
protect it against potentially damaging conditions. Some
of these systems are as follows
Alarms:
•
High Temperature
•
Low Oil Pressure
•
Overcrank
•
Overspeed
•
Underspeed
Warnings:
•
Charger Warning
•
Charger Missing AC
•
Low Battery
•
Exercise Set Error
•
USB Warning
•
Download Failure
2.4 — Specifications
2.4.1— Generator
Model
Rated Voltage
Rated Maximum Load Current
(Amps) at 220 Volts (LP)*
Main Circuit Breaker
Phase
Rated AC Frequency
Battery Requirement
Weight (kilos/ lbs.)
Enclosure
Normal Operating Range
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator Assemblies, and CSA-C22.2 No. 100-04 Standard
for Motors and Generators.
* Natural Gas ratings will depend on specific fuel joules/Btu content. Typical derates are between 10-20% off the LP gas rating.
** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer switch.
6
•
RPM Sensor Loss
•
Controller Fault
•
Wiring Error
•
Overvoltage
•
Undervoltage
•
Fuse Problem
•
Overload
•
Stepper Overcurrent
8kVA
36.4 / 34.8 / 33.3
40 Amp
175.4/387
Steel
This unit is tested in accordance to UL 2200 standards with an operating temperature of -20 ºF (-29 ºC) to 122 ºF (50 ºC).
For areas where temperatures fall below 32 ºF (0 ºC) a cold weather kit is recommended. When operated above 77 ºF (25
ºC) there may be a decrease in engine power. (Please reference the engine specifications section.
The control panel contains a display which alerts the
operator when a fault condition occurs. The above list is
not all inclusive. For more information about alarms and
control panel operation, see Section 3 Operation.
NOTE: A warning will indicate a condition, on the gener-
ator, that should be addressed but not shut the generator
down. Am alarm will shut the generator down to protect
the system from any damage. In the event of an alarm,
an owner can clear the alarm and restart the generator
prior to contacting an independent servicing dealer. If the
intermittent issue occurs again, contact an independent
servicing dealer.
2.3 — Emission Information
The engine used in this generator is not certified to
United States EPA emission standards, or any other emis-
sion standards. Sale or use of this generator is not legal
in the U.S. or any country which has emission standards
that are applicable to this product.
10kVA
220/230/240
45.5 / 43.5 / 41.7
50 Amp
1
50 Hz
Group 26R, 12 Volts and 525 CCA Minimum
197.3/435
Steel
Owner's Manual for 50 Hz Air-cooled Generators
13kVA
59.1 / 56.5 / 54.2
63 Amp
213.6/471
Steel