Maintenance
Remove the battery and store it in a cool, dry room
11.
on a wooden board. Never store the battery on any
concrete or earthen floor.
Clean and wipe down the entire generator.
12.
4.11.2— Return to Service
To return the unit to service after storage:
Verify that utility power is turned off.
1.
Check the tag on the engine for oil viscosity and
2.
classification. If necessary, drain and refill with
proper oil.
Check the state of the battery. Fill all cells of
3.
unsealed batteries to the proper level with distilled
water. DO NOT use tap water. Recharge the bat-
tery to 100% state of charge. If defective, replace
the battery.
Clean and wipe down the entire generator.
4.
Make sure the 7.5 Amp fuse is removed from the
5.
generator Control Panel.
Reconnect the battery. Observe battery polarity.
6.
Damage may occur if the battery is connected
incorrectly. Install positive cable first.
Reconnect the battery charger AC input T1/Neutral
7.
cable (has white sleeve) at controller.
Open the fuel shutoff valve.
8.
Insert the 7.5 Amp fuse into the generator control
9.
panel.
Start the unit by pressing the MANUAL button.
10.
Allow the unit to warm up for a few minutes.
Stop the unit by pressing the control panel OFF
11.
button.
Turn on the utility power to the transfer switch.
12.
Set the control panel to AUTO.
13.
The generator is ready for service.
NOTE: When a battery is dead or has been discon-
nected, the exercise timer and current date and time
must be reset.
20
Owner's Manual for 50 Hz Air-cooled Generators