Operation
3.2 — Using the Auto/Off/Manual Buttons
Button
Selecting this button activates fully automatic system operation. It also allows the unit to automatically
Auto
start and exercise the generator according to the exercise timer (see the Setting the Exercise Timer
section).
Off
This button shuts down the engine and also prevents automatic operation of the unit.
This button will crank and start the generator. Transfer to standby power will not occur unless there is a
Manual
utility failure.
NOTE: Damage caused by mis-wiring of the interconnect wires is not warrantable.
3.3 — Interface Menu Displays
The LCD display:
Feature
The default page which will be displayed if no buttons are pressed for 60 seconds. This page normally
shows the current Status message and the current date and time. The highest priority active Alarm/
HOME page
Warning will be automatically posted on this page as well as flashing the backlight when such a condi-
tion is detected. In the case of multiple Alarms/Warnings, only the first message will be displayed. To
clear an Alarm or Warning, press the OFF button and then press the ENTER key.
Normally off. If the operator presses any button, the backlight will automatically light and remain on for
Display Backlight
30 seconds.
Allows the operator to navigate to all other pages or sub-menus by using the Arrows and Enter but-
tons. This page can be accessed at any time with several presses of the dedicated Escape button.
MAIN MENU page
Each press of the Escape button takes the operator to the previous menu until the MAIN MENU dis-
plays. This page contains information for - History; Status; Edit; Debug.
3.3.1— Menu System Navigation
To get to the MENU, use the "Escape" button from any page. It may require pressing it many times before getting to the
MENU page. Navigate to the desired menu by using the
press the "Enter" button. See Figure 3-3.
10
Description of Operation
Description
↑
↓
/
buttons. When the desired menu is displayed and flashing,
Owner's Manual for 50 Hz Air-cooled Generators