PROFINET IO configuration

This web page is used to configure all the parame-
ters relevant to the PROFINET IO protocol standard.
All settings can also be configured from a standard
PROFINET IO configuration tool, for instance Sie-
mens Primary Setup Tool (PST). The tool is available
on the Internet.
Fig. 9
RealTime Ethernet Protocol Configuration - PROFINET IO
Object
Description
Device Name
The name of the PROFINET IO device. The name must be unique.
IP Address
The static IP address for the module on the PROFINET IO network.
Subnet mask
Configure the subnet mask for the module on the PROFINET IO network.
Gateway
Configure the default gateway for the PROFINET IO network.
The module can be configured to automatically obtain the IP address from a DHCP ser-
Use DHCP
ver on the network.
The module can be put in product simulation mode to generate realistic simulated
values of all the PROFINET IO input data modules. It will thus be possible to connect a
PROFINET IO master to a module fitted in a CIU or an E-box without installing this
device in a real industrial process system. In an office environment, it can then be veri-
Grundfos pro-
fied that communication works and data are received and handled correctly by the
duct simulation
PROFINET IO master application program (e.g. PLC program) before installing the
device.
To enable product simulation, select a product type from the dropdown list.
To terminate product simulation, switch the module off and on.