9. RELEASE
To move the gate manually it is necessary to release the gearmotor inserting the special key, turning it for 90° and lift up the
lever (Fig. 13, 14).
In order to carry out the manual operation of the gate leaf the followings must be checked:
- That the gate is endowed with appropriate handles;
- That these appropriate handles are placed so to avoid safety risks for the gearmotor;
- That the physical effort necessary to move the gate leaf should not be higher than 225 N, for doors/gates for private dwellings,
and, 390N for doors/gates for commercial and industrial sites ( values indicated in 5.3.5 of the EN 12453 norm).
Fig. 13 Lock motor
10. RISOLUZIONE PROBLEMI
PROBLEM
By giving a command with the remote
control or with the key selector, the
gate doesn't open or the motor doesn't
start.
By giving a command with the remote
control, the gate does not open, but it
works with the key selector.
The gate starts, but stops immediately
One wing opens and the other closes
24 / 52
Fig. 14 Unlock motor
PROBABLE CAUSE
230 volt mains voltage absent.
Emergency STOP present.
Fuse blown.
Power cable of motor not connected or
faulty.
The photocell is not functioning or the
beam is interrupted.
The remote control has not been
memorized or the battery is flat.
The torque of the motor is insufficient.
The value of the obstacle sensitivity
(if present) it is not suitable for the
installation.
The wire connection is not correct.
SOLUTION
Check the main switch.
Check for any STOP selectors or
commands.
If not used, check the jumper on the
STOP input of the control unit.
Replace with one of same value.
Connect the cable to the appropriate
terminal board or replace it.
Check the connection, remove any
obstacle across the beam.
Carry out the remote control learning
procedure on the control unit or replace
the battery with a new one.
Modify the value of the torque in the
control unit.
Modify the value of the sensitivity in the
control unit, if possible.
Carry out the learning of the stroke with
the BIOS2 / BIOS2 ECO control unit.
Invert the connection of the cable of the
motor