Automatic Equalization - Victron energy BlueSolar MPPT 150/35 Manual De Instrucciones

Ocultar thumbs Ver también para BlueSolar MPPT 150/35:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

3.7.1 Automatic equalization

Automatic equalization is def ault set to "OFF". By using the
conf iguration tool mpptpref s this setting can be conf igured with a
number between 1 (ev ery day ) and 250 (once ev ery 250 day s).
When automatic equalization is activ e, the absorption charge
will be f ollowed by a v oltage limited constant current period (see
table in section 3.5). The current is limited to 8% of the bulk
current f or all VRLA (Gel or AGM) batteries and some f looded
batteries, and to 25% of the bulk current f or all tubular plate
batteries and the user def ined battery ty pe. The bulk current is
the rated charger current unless a lower maximum current
setting has been chosen.
In case of all VRLA batteries and some f looded batteries
(algorithm number 0, 1, 2 or 3) automatic equalization ends
when the v oltage limit maxV has been reached, or af ter
t = (absorption time)/8, whichev er comes f irst.
For all tubular plate batteries and the user def ined battery ty pe
automatic equalization ends af ter t = (absorption time)/2.
When automatic equalisation is not completely f inished within
one day , it will not resume the next day , the next equalisation
session will take place as determined by the day interv al.
3.8 Connectivity
Sev eral parameters can be customized (VE.Direct to USB
cable, ASS030530000, and a computer needed). See the data
communication white paper on our website.
The required sof tware can be downloaded f rom
http://www.v ictronenergy .nl/support-and-downloads/sof tware/
The charge controller can be connected the to a Color Control
panel, BPP000300100R, with a VE.Direct to VE.Direct cable.