Reset of the charge algorithm:
The default setting for restarting the charge cycle is
Vbatt < (Vfloat – 0,4V) for lead-acid, and Vbatt < (Vfloat – 0,1V) for LiFePO4
batteries, during 1 minute.
(values for 12V batteries, multiply by two for 24V)

3.9 Automatic equalization

Automatic equalization is default set to 'OFF'. With the Victron Connect app
(see sect 1.12) this setting can be configured with a number between 1
(every day) and 250 (once every 250 days).
When automatic equalization is active, the absorption charge will be followed
by a voltage limited constant current period. The current is limited to 8% or
25% of the bulk current (see table in sect. 3.5). The bulk current is the rated
charger current unless a lower maximum current setting has been chosen.
When using a setting with 8% current limit, automatic equalization ends
when the voltage limit has been reached, or after 1 hour, whichever comes
first.
Other settings: automatic equalization ends after 4 hours.
When automatic equalization is not completely finished within one day, it will
not resume the next day, the next equalization session will take place as
determined by the day interval.
3.10 Pluggable LCD display - Live data
Remove the rubber seal that protects the plug on the front of the controller
and plug-in the display module. The display is hot-swappable; this means
that the charger may be operational while the display is plugged in.
The following information will be displayed if the "-" button is pressed (in
order of appearance):
Displayed info
Battery voltage and charge current
Battery charge current
Battery voltage
Battery charge power
Battery temperature
(1)
Charger temperature
(1)
Panel current
Panel voltage
Panel power
Warning message
(2)
Error message
(2)
Remote operation
(2)
BMS operation
(2)
Notes:
1) A valid temperature is shown, --- = no sensor information or Err = invalid sensor data.
2) These items are only visible when relevant.
12
Icons Segments
Units
 A
.
. A
. V
. W
.,, °C/°F
.,, °C/°F
. A
. V
. W




