Danfoss ERC213 Manual Del Usuario página 6

Ocultar thumbs Ver también para ERC213:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 40
3 - Quick Configuration at Power Up
STEP 1: Power on
y
STEP 2: Select the quick configuration menu
y
Within 30 seconds of power on, press "<" BACK for 3 seconds.
The main switch "r12" is automatically set to OFF.
STEP 3: Select pre-installed application "o61"
y
The display automatically shows the application selection parameter "o61".
Press SET to select the pre-installed application.
The display shows the default value (eg. "AP0" flashing).
Choose the application type by pressing UP/DOWN and press SET to confirm.
The controller presets parameter values according to the selected application and does not hide relevant parameters.
Tip: you can easily move from AP0 to AP6, and thus select the simplified list of parameters, by pressing the UP key
(circular list).
App
App 0
App 1
App 2
App 3
App 4
App 5
App 6
| 6
Description
None (no preset application)
Medium temperature ventilated refrigeration units (2 – 6 °C), with timed natural defrost
Medium temperature ventilated refrigeration units (0 – 4 °C), with timed electrical defrost
Low temperature ventilated refrigeration units (-26 – -20 °C), with timed electrical defrost
Medium temperature ventilated refrigeration units (0 – 4 °C), with electrical defrost (by temperature)
Low temperature ventilated refrigeration units (-26 – -20 °C), with electrical defrost (by temperature)
None (no preset application) with simplified parameter list
Instruction sheet | ERC 213
DKRCC.EI.RL0.G2.ML/520H9654

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Erc 213Erc214

Tabla de contenido