Megger DM80/2 Serie Guia Del Usuario página 14

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Application Notes
longer e.g. long supply cables. The absorption
current decreases relatively slowly compared
with the charging current. In essence it
depends upon the nature of the insulation
material.
The conduction or leakage current builds up
quickly to a steady value and then remains
constant for a particular applied voltage under
stable conditions. It is this current that is
affected by moisture, dirt etc. and the degree
to which it flows bears a direct relation to the
quality of the insulation, and consequently to
the
value
of
the
insulation
resistance
measured. An increase in the leakage current
is a pointer to possible future problems.