PLAYA - USE AND MAINTENANCE
ANTI STAGNATION FUNCTION (AUTOMATIC)
It is an automatic function that activates the blower for 30 seconds and the filter
pump for 3 hours when the latter has been off for more than 48 hours.
MINIMUM TEMPERATURE FUNCTION (AUTOMATIC)
It allows you to prevent the water from cooling to ambient temperature, thus
minimizing the energy consumption and the time to bring the temperature of use.
It is automatically activated when the "water heating" function is turned off. It is
to regulate the temperature with the same function mode "Heating water using the
reference temperature = 10 °C". For the hysteresis, use the fixed value of 1 ° C.
The following table summarizes all the signal codes of alarms, with their
descriptions, that the control unit is capable of signaling.
DISPLAYED
MESSAGE
no alarm, but
the controller's
display does
not turn on
FLOW
52
ALARM SIGNALS
ACTIONS TAKEN
ITEM THAT
FROM THE
GENERATED THE
CONTROL SYSTEM
--
--
filter pump
the flow switch
turned off,
has detected
heater switched
insufficient
off if turned on
flow
POSSIBLE
CAUSES
ALARM
lack of power.
Fuse of the
controller
interrupted
clogging of the
suction circuit
(prefilter
basket clogged,
clogged filter,
any foreign
body in the
pump impeller)
RECOVERY MODE
check the power
supply line. Check
the fuse of the
control unit
after removing the
cause, the alarm is
reset by pressing
the button "Filter
pump"
and then the
"hand" button
if, prior to the
alarm, the heater
was turned on,
the reset is active
again after 3
minutes.