18
en
6.
Connecting the FAS-420 Series
NOTICE!
The units are usually connected to an additional power supply. When connecting to the FPA-
5000 Modular Fire Panel, the voltage is supplied via the AUX outputs of the BCM 0000 Battery
Controller Module. Alternatively, an external power supply unit (e.g. FPP-5000 or UEV 1000)
can be used.
See Figure 4, Page 5.
Designation
Shield
* Digital parallel displays for series FAS-420 are available by separate order.
LSN Configuration
Once the aspirating smoke detector has been connected to the LSN, the detector and the
detector module or the two detector modules (FAS-420-TP2 and FAS-420-TT2) are configured
using the RPS programming software via a laptop connected to the FPA-5000 fire panel.
NOTICE!
Both a dual-detector dependency and a dual-zone dependency can be established when
connecting the FAS-420 Series to the FPA-5000 Modular Fire Panel.
Parameter Settings via RPS
The parameters for each detector module are specified in the relevant "Sensor" dialog window
via drop-down fields. The default settings in RPS are in bold in each case.
1.
2.
F.U01.029.274 | 4.0 | 2010.12
FAS-420-TP1 | FAS-420-TP2 | FAS-420-TT1 | FAS-420-TT2 | FAS-420-TP1-SL | FAS-420-TP2-SL |
Wire the unit according to the connection information described below. The connection
terminals of the 24 V additional supply voltage and the LSN connection are plug
connections and are easy to remove.
Cable
-
b1+
Yellow
a1-
White
b2+
Yellow
a2-
White
V+
Red
V-
Black
V+
Red
V-
Black
V+
Red
V-
Black
D+
-
D-
-
Enter the used detector module.
Select all other parameters (see tables).
Function
Shield wire
LSN b, incoming
LSN a, incoming
LSN b, outgoing
LSN a, outgoing
Additional power supply, incoming
Additional power supply, outgoing
Supply voltage for digital parallel display *
Data line connection for digital parallel display *
FAS-420-TT1-SL | FAS-420-TT2-SL
Bosch Sicherheitssysteme GmbH