Special settings

Open the special settings menu
1. Keep the programming button (PROG button) (D) pressed in for approximately 3 seconds. The display
shows "3".
2. Press the programming button (PROG button) (D) again. The display shows "4".
3. Keep the programming button (PROG button) (D) pressed in again for approximately 3 seconds. The display
shows "5".
Menu 5 + Menu 6:
Force limitation for Open and Close
Warning:
If the setting is too high, persons may be placed at risk of injury.
In the delivery state, the set value is "6" on opening and "4" on closing.
1. Select menu item "5".
After about 2 seconds, the display blinks and the set value of the power limit for upward motion appears.
2. If desired, adjust the setting with the aid of the OPEN (B) and CLOSE (C) buttons.
3. Press the programming button (PROG button) (D).
The display shows "6". After about 2 seconds the display and the set value for the power limit for closure
appears.
4. If desired, adjust the setting with the aid of the OPEN (B) and CLOSE (C) buttons.
Warning:
The force on the main closure side must not exceed 400 N / 750 ms!
5. Press the programming button (PROG button) (D).
The display shows "7".
N-423
Installation
45