Ed
Description
Ct17
1
Does the IED accept a Select/SelectWithValue
from the same client when the control object is
already selected (Tissue #334)
Ct18
1,2
Is for SBOes the internal validation performed
during the SelectWithValue and/or Operate
step
Ct19
-
Can a control operation be blocked by Mod=Off
or [On-]Blocked (Compare PIXIT-Sr5)
Ct20
1,2
Does the IED support local / remote operation
Ct21
1,2
Does the IED send an InformationReport with
LastApplError as part of the Operate response-
for control with normal security
Ct22
2
How to force a "parameter-change-in-
execution"
Ct23
1,2
How many SBOns/SBOes control objects can be
selected at the same time?
Ct24
1,2
Can a controllable object be forced to keep its
old state e.g. Internal Controllable Objects may
not be accessible to force this, whereas a switch
like Circuit Breaker outside the DUT can?
Ct25
1,2
When CDC=DPC is supported, is it possible to
have DPC (Controllable Double Point) go to the
intermediate state? (00)
Ct26
1,2
Name a DOes point (if any) with a finite
operate timeout and specify the timeout
(in milliseconds)
Ct27
2
Does the IED support control objects with
external signals?
<additional items>
Value / Clarification
SBOns:
N
SBOes:
N
The validation is performed during
the Operate step
Deprecated
Y
SBOns: N
DOns:
N
N/A
SBOns: multiple
SBOes: multiple
Y
Y
CTRL/CSWI1.Pos
Timeout is configurable
DOns:
Y
SBOns:
Y
DOes:
Y
SBOes:
Y