◙ INDICATOR LEDS:

Located on the regulator display, you will find three indicator leds indicating the following,
from left to right:
4. Condition of the unit (ON/OFF)
5. Defrosting (ON/OFF)
6. Compressor (ON/OFF)
◙ ALARMS:
The unit will display the following alarm codes when necessary:
F1: Failure ambient air indicator.
F2: Failure evaporation indicator.
F3: Failure resistance indicator.
F4: Failure Relative Humidity indicator.
HP: High pressure alarm.
LP: Low pressure alarm.
TH: Thermal compressor alarm.
AH: Maximum air return exceeded alarm.
AL: Minimum air return exceeded alarm.
HT: Maximum resistance temperature exceeded / Water valve exceeded.
◙ ALARM CANCELLATION:
In order to cancel the alarm codes which may be displayed, push the UP & DOWN buttons
simultaneously for a few seconds. If the problem still exists, the alarm will show it immediately.
Maintenance:
Clean the surface of the controlling unit with a soft cloth, soap and water. Never use
abrasive products, gasoline, alcohol or solvent.
Warnings:
Not respecting the manufacturer's instructions regarding the use of this equipment may
compromise the operation and safety of the equipment.
8.
GENERAL PRECAUTIONS.
The installation, start-up and maintenance should be done by qualified personnel only.
This equipment should not be exposed to inflammable substances or explosives.
For any maintenance work done on the inside of the machine, proper care and precaution
should be taken to disconnect the main equipment from the power supply. For these types of
operations, the use of protective equipment such as goggles and gloves is required.