11. REQUIREMENTS AND PROCEDURES.
It is important that the equipment be installed on stable, horizontal ground.
Always place the equipment vertically and far away from dangers of inundation. If not, the
warranty will be voided.
Like any other electrical equipment, the dehumidifier should be installed more than 2
meters, horizontally, away from the pool (Volume 2) and 2,5 meters, vertically, away from
the pool.
The machine is equipped with a one-meter hose for the elimination of condensed water.
During operation, condensed water will appear, produced by the passing of air through the
evaporation unit. For this, the machine is equipped with a drainage tube on the base. Please plan
ahead for the drainage.
This equipment is designed for interiors, the air inlets and outlets should be free of
obstruction. Obstacles should be maintained at a distance.
The equipment includes a support kit for wall, floor or wheels.
12. ELECTRICAL CONNECTIONS.
The electrical installation should be done by qualified professionals, keeping in mind the following
points:
Connect the equipment following the wiring diagram included in this manual.
Place a U-curve thermal-magnetic circuit breaker in the general power connection to
protect the line in the case of a short in the circuit.
Place a differential circuit breaker in the general power connection to protect the
equipment from possible grounding problems. The differential breaker should be minimum
30 mA.
◙ Differential circuit breaker.
◙ Circuit breakers or thermal-magnetic circuit breaker.
The picture shown below is a diagram of how the connections should be made.
ENGLISH
35