Non-Dimming
Load
The configuration process establishes the appropriate parameters for the FSP-221B operation. This is done through the FSIR-100
configuration tool. If no configuration steps are taken, the sensor will use its default parameter values.
The FSIR-100 Wireless IR Configuration Tool is a hand-held tool for changing default parameter values and testing the FSP-221B. It
provides wireless access to the FSP-221B sensors for parameter changes and testing.
The FSIR-100 display shows menus and prompts to lead you through each process. The navigation pad provides a simple way to
navigate through the customization fields.
Within a certain mounting height of the sensor, the FSIR-100 allows modification of the system without requiring ladders or tools; simply
with a touch of a few buttons.
The FSIR-100 IR transceiver allows bi-directional communication between the FSP-221B and the FSIR-100 configuration tool . Simple
menu screens let you see the current status of the sensor and make changes. It can change FSP-221B sensor parameters such as
high/low mode, sensitivity, time delay, cut off and more. With the FSIR-100 you can also establish and store FSP-221B parameter
profiles.
The FSIR-100 operates on three standard 1.5V AAA Alkaline batteries or three rechargeable AAA NiMH
batteries. The battery status displays in the upper right corner of the display. Three bars next to BAT=
indicates a full battery charge. A warning appears on the display when the battery level falls below a
minimum acceptable level. To conserve battery power, the FSIR-100 automatically shuts off 10 minutes
after the last key press.
• If communication is not successful, (if possible) move closer to the sensor.
• If still not successful, there may be too much IR interference from other sources. Programming
the unit at night when there is no daylight available may be the only way to communicate with the
sensor.
Navigate from one field to another using (up) or (down) arrow keys. The active field is indicated by
flashing (alternates) between yellow text on black background and black text on yellow background.
Once active, use the Select button to move to a menu or function within the active field. Value
fields are used to adjust parameter settings. They are shown in "less-than/greater-than" symbols:
<value>. Once active, change them using(left) and(right) arrow keys. The right key increments and
the left key decrements a value. Selections wrap-around if you continue to press the key beyond
maximum or minimum values. Moving away from the value field overwrites the original value. The
Home button takes you to the main menu. The Back button can be thought of as an undo function.
It takes you back one screen. Changes that were in process prior to pressing the key are lost.
NOTE: When you change parameter values on the FSP-221B, you need wait about 3 minutes
before the new parameters are saved into the memory.
Neutral or
Phase B
White with
Black Stripes
Load
(Red)
Violet
Gray
Neutral or
Phase B
Black Line or
Phase A
FSP-221B CONFIGURATION
USING THE FSIR-100 CONFIGURATION TOOL
WIRING
Dim (+)
Violet
Dim (-)
Gray
BATTERIES