1. Box contents

SANICONDENS Clim mini comprises two components:
- Pump unit
- Triple-level sensor
1: pump
2: level sensor
2a: lid
2b: float ball
2c: filter
2d: reservoir
2e: stopper
3: rubber elbow
4: pipe 1.2m, Øint 4.6mm
5: vent connection.
6: cable with coupler
7: support bracket

2. Warning notice

SANICONDENS Clim mini
- Designed only for pumping water.
- State-of-the-art electrical installation.
- Must not run dry.
- Install all level sensors horizontally.
- Install indoors only (domestic or indus-
trial premises).

3. Technical data

Sound level at 1 m
23 dB(A)
Maxi. flow rate
15 l/h
Maxi. horizontal discharge
14 m
Maximum vertical
6 m
discharge
Maximum air vent length
2 m
Electricity supply
220-240V - 50-60Hz
Power
22 W
Thermal protection
Trips at 80°C and then
automatically resets
Maximum temperature
35°C
of water
4. Installation
A – Level Sensor unit
Magnet facing upwards.
4
Cover on.
4
Connect the short pipe (150mm)
4
to the lid vent, point it upwards
and secure.
Fit the level sensor horizontally
4
using the support supplied.
B – Pump unit
Install the pump in the trunking
4
1
Make sure the the pump is pointing in the right direction (see arrows on the
pump unit).
Install the pump vertically (preferably).
4
Make sure there is enough room around the pump unit for it to cool off in the
4
event of prolonged usage.
Ensure that electrical connections are not exposed to water.
4
SANICONDENS Clim mini is guaranteed for two years subject to correct installation and usage.
notice clim mini 2018.indd 3
- Do not submerge.
- Unplug the appliance prior to
maintenance.
- Point the float ball with the magnet
upwards
Height in metres
16
14
12
10
8
6
4
2
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Litres per hour
or in the suspended ceiling
.
2
2
1
SANICONDENS Clim mini
C – Hydraulic connections
Feed the incoming condensate to the level sensor inlet (1).
4
Connect the pump and the level sensor up using the pipe supplied (2).
4
Evacuation (3):
4
• The pump outlet must be connected to the waste water discharge
using a suitable fitting with an inner diameter of 8 to 10mm
(not supplied).
• Warning: To prevent siphoning, the discharge outlet must be
higher than the condensate tank.
D – Electric connections
Connect the level sensor to the pump unit using the cable.
4
To connect the alarm, there are
4
(usually open/ usually closed) contacts,
recommended interrupting capacity = 2A (5Maxi).
Connect the alarm as shown in the wiring
setup diagram.
Electricity supply:
4
• Plug the pump in (phase, earth, neutral):
- either by way of the air conditioner
- or directly using a 30-mA circuit breaker.
5. Start-up
Check pumping direction
4
(see arrow on the pump unit).
Introduce water into the level sensor.
4
Check that the pump starts up and then stops
4
once the water level has dropped.
Check that the connections are all waterproof.
4
6. Maintenance
Condensate tank Level Sensor
Maintenance must only be carried out with the appliance switched off.
4
This product must be maintained at the start of each summer season, or regu-
4
larly if the pump is used year round.
Clean:
4
• the reservoir,
• the filter,
• the float ball.
• Replace all items and close the reservoir.
SFA
3
2
1
2
white
NF
NO
black
purple
Discharge pipe (not supplied)
09/10/2018 18:22