Siemens POINTEK CLS100 Serie Guia De Inicio Rapido página 12

Ocultar thumbs Ver también para POINTEK CLS100 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 67
Enclosure Version* and Fully Synthetic Process
Connection Version**
– ground
WARNING: A wet location is a location where water or other
conductive liquid may be present and is likely to increase the risk of
electric shock.
Page EN-10
Pointek CLS100 – QUICK START MANUAL
Terminal Operation
cable equiv.
mA current loop (+V or -V)
red wire
mA current loop (-V or +V)
black wire
cable shield connection
cable shield
relay**/solid state switch*
white wire
relay**/solid state switch*
white wire
*Solid State Switch
Max. switching voltage: 30 V DC
or 30 V AC
Max. switching current: 82 mA
**Relay Contact Load
Max. switching voltage: 30 V AC
or 60 V DC; limited to 35 V DC or
16 V AC max. in wet locations.
Max. switching current: 1 A
Max. switching power: 60 W
7ML19985QJ83