Tripp-Lite SmartOnline S3MX Manual Del Propietário página 35

Sistemas ups trifásicos
Ocultar thumbs Ver también para SmartOnline S3MX:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
4. Control Panel and LCD Operations
4.2.5.4 Pre-Alarm Screen
The Pre-Alarm Screen Setup and Setting options are shown in Figure 4.17 and Table 4.10. The Pre-Alarm Setting can be accessed in any
operation mode.
Table 4.10: Setup Pre-Alarm Setting List
Setting Item
Sub Item
Line Voltage Range
--
Line Frequency
--
Range
Load
--
Figure 4.17 Setup-Pre-Alarm Screen
Explanation
Set line voltage range:
Upper limit
• +5%
• +10%
• +15%
• +20% (Default)
Lower limit
• -5%
• -10%
• -15%
• -20% (Default)
Set line frequency range:
Upper / Lower limit
• +/- 1 Hz
• +/- 2 Hz
• +/- 3 Hz
• +/- 4 Hz (Default)
Set UPS overload percentage (40~100%)
• 100% (Default)
Set UPS load unbalance percentage (20~100%)
• 100% (Default)
35

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

S3m100kx, s3m120kx, s3m160kx, s3m200kx

Tabla de contenido