3. Installation and Setup

3.2.1 Interface and Communication

These UPS systems come equipped with various communication devices. Please refer to section 5. Interface and Communication for
further details.

3.2.2 Power Stage/Module

Each power stage/module includes a power factor correction rectifier, a battery charger, an inverter and control circuit.
No.
Item
1
Fan
Stage Address DIP
2
Switches
3
Battery Start Button
4
FAULT LED
5
RUN LED
Description
Air enters the power stage through the front grills and is exhausted through the rear of the module. Do not
block the ventilation vent.
There are three DIP switches for Power Stage address setting. In the same cabinet, each Power Stage ID
MUST be exclusive. Refer to Table 3.1 Power Stage ID for more information.
When AC input is not available, use this button to start UPS battery power.
ON
ON/OFF 0.5 sec
ON
ON/OFF 0.5 sec
ON/OFF 0.15 sec
1
Dry Contact Port X1 (Optional battery temperature
compensation thermostat)
2
Dry Contact Port X2 (EPO)
3
SNMP Slot (Optional WEBCARDLX or RELAYCARDSV card)
4
RS-232 Port
5
USB Port
The power stage is in fault condition.
The power stage IDs are in conflict.
The power stage normally works as a secondary stage.
The power stage normally works as a primary stage.
The CAN Bus communication does not work.