Maintenance Bypass Operation; Transfer Critical Load From Line Mode To Maintenance Bypass - Tripp-Lite SmartOnline S3MX Manual Del Propietário

Sistemas ups trifásicos
Ocultar thumbs Ver también para SmartOnline S3MX:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
7. UPS Operation

7.3 Maintenance Bypass Operation

Follow the below steps to transfer to maintenance bypass for power stage maintenance and UPS protection.

7.3.1 Transfer Critical Load from Line Mode to Maintenance Bypass

Confirm Bypass Mode is enabled via the LCD display menu prior to performing the Maintenance Bypass procedure.
Remove the mechanical locking plate securing the switch (S3M100KX model) or Q4 Maintenance Bypass breaker
Step 1
(S3M120KX, S3M160KX and S3M200KX models).
S3M100KX (100 kVA)
Confirm the UPS is operating in Bypass Mode.
Step 2
Step 3
Rotate switch to BYPASS (S3M100KX model), or Turn ON the Q4 Maintenance Bypass breaker (S3M120KX, S3M160KX
and S3M200KX models).
S3M100KX (100 kVA)
Step 4
Turn OFF the Q3 Output breaker.
Q4
Maintenance Bypass
S3M120KX (120 kVA) S3M160KX/S3M200KX
ON
OFF
Q4
Maintenance Bypass
S3M120KX (120 kVA) S3M160KX/S3M200KX
57
Q4
Maintenance Bypass
(160 kVA/200 kVA)
2018/01/01
OFF
ON
Q4
Maintenance Bypass
(160 kVA/200 kVA)

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

S3m100kx, s3m120kx, s3m160kx, s3m200kx

Tabla de contenido